D6680
D6680 Installation Guide
50084D
Page 2
© 2003 Radionics
2.0
Specifications
Protocols Supported
ARP, UPD, TCP, Telnet, ICMP, SNMP, DHCP, TFTP, HTTP, BootP and
ECHO
Serial:
DB25
RS-232/RS-322/RS-485 serial port with DCE configuration
DB9
RS232 serial port with DTE configuration
Connectors
Network:
10BASE-T or 10BASE-FL
LAN/WAN:
‘RJ-45’ Modular Jack (Ethernet)
Ethernet
Category 3 or better unshielded twisted pair
Max Length:
328 ft. (100 m)
Cables
RS-232
Max Length:
50 ft.
Data Rates
Serial speed ranging from 300 bps to 115.2 kbps
Characters:
7 or 8 data bits
Stop bits:
1 or 2
Serial Line
Formats
Parity:
Odd, even, none
Modem Controls
RTS, CTS, DSR, DCD, DTR
Flow Control
XON/XOFF
CTS/RTS
Management
HTTP (internal web server)
SNMP (read only)
Serial login
Telnet login
System Software
Flash ROM standard: downloadable from a TCP/IP host (TFTP) or over
serial port
Diagnostic LEDs
Network Transmit, Network Receive, Good Link, Collisions, Channel 1
Status, Channel 2 Status, Diagnostic
Compatibility
Ethernet: Version 2.0/IEEE 802.3
D6600
Power Requirements
9 to 30 VDC or 9 to 25 VAC (External adapter included)
Power Consumption: 3 W
AC Current Required
UPS Standby Current: 35 mA
Power Input
AC nominal operating range 120 or 240 VAC
AC maximum operating range 100 to 240 VAC ~ 50/60 Hz
0.2 Amp maximum
Standby Power
An Uninterrupted Power Supply is required for use with the D6680, when
used for UL FIRE Protective Signaling Systems. A 60-hour minimum UPS
standby power supply is required for UL Certification.
Operating Temperature
+41
°
F to +122
°
F (+5
°
C to +49
°
C)
Environmental
Storage Temperature
-40
°
F to +151
°
F (+40
°
C to +66
°
C)
Unit
6.5 in. x 4.46 in. x 1.39 in. (16.5 cm x 11.3 cm x 36 mm)
Dimensions
Enclosure
(H x W x D)
The enclosure is manufactured from 20 Gauge (1.0 mm),
cold-rolled steel. A keyed lock is included.
12.5 in. x 14.5 in. x 3 in. (31.8 cm x 36.8 cm x 76 mm)
Weight
1.1 lbs. (0.48 kg)
Table 1: D6680 Specifications