2.0

Specifications

Protocols Supported

ARP, UPD, TCP, Telnet, ICMP, SNMP, DHCP, TFTP, HTTP, BootP and
ECHO

Serial:

DB25 

RS-232/RS-322/RS-485 serial port with DCE configuration

DB9 

RS232 serial port with DTE configuration

Connectors

Network:

10BASE-T or 10BASE-FL
LAN/WAN:

‘RJ-45’ Modular Jack (Ethernet)

Ethernet

Category 3 or better unshielded twisted pair
Max Length:

328 ft. (100 m)

Cables

RS-232

Max Length:

50 ft.

Data Rates

Serial speed ranging from 300 bps to 115.2 kbps

Characters:

7 or 8 data bits

Stop bits:

1 or 2

Serial Line
Formats

Parity:

Odd, even, none

Modem Controls

RTS, CTS, DSR, DCD, DTR

Flow Control

XON/XOFF
CTS/RTS

Management

HTTP (internal web server)
SNMP (read only)
Serial login
Telnet login

System Software

Flash ROM standard: downloadable from a TCP/IP host (TFTP) or over
serial port

Diagnostic LEDs

Network Transmit, Network Receive, Good Link, Collisions, Channel 1
Status, Channel 2 Status, Diagnostic

Compatibility

Ethernet: Version 2.0/IEEE 802.3
D6600

Power Requirements

9 to 30 VDC or 9 to 25 VAC (External adapter included)
Power Consumption: 3 W

AC Current Required

UPS Standby Current: 35 mA

Power Input

AC nominal operating range 120 or 240 VAC
AC maximum operating range 100 to 240 VAC ~ 50/60 Hz
0.2 Amp maximum

Standby Power

An Uninterrupted Power Supply is required for use with the D6680, when
used for UL FIRE Protective Signaling Systems. A 60-hour minimum UPS
standby power supply is required for UL Certification.

Operating Temperature

+41

°

F to +122

°

F (+5

°

C to +49

°

C)

Environmental

Storage Temperature

-40

°

F to +151

°

F (+40

°

C to +66

°

C)

Unit

6.5 in. x 4.46 in. x 1.39 in. (16.5 cm x 11.3 cm x 36 mm)

Dimensions

Enclosure
(H x W x D)

The enclosure is manufactured from 20 Gauge (1.0 mm),
cold-rolled steel. A keyed lock is included.

12.5 in. x 14.5 in. x 3 in. (31.8 cm x 36.8 cm x 76 mm)

Weight

1.1 lbs. (0.48 kg)

Table 1: D6680 Specifications

Summary of Contents for D6680

Page 1: ... not attempt to connect both Ethernet ports simultaneously The D6680 does not have routing capabilities The D6680 has the following items on the Network Interface end of the unit 1 10BASE T Ethernet Port refer to Figure 2 2 10BASE FL Ethernet Port Transmit Not Used 3 10BASE FL Ethernet Port Receive Not Used 4 Network LEDs 5 Power Plug 1 1 1 RJ 45 10BASE T Ethernet Port Figure 2 RJ 45 Ethernet Jack...

Page 2: ...port Diagnostic LEDs Network Transmit Network Receive Good Link Collisions Channel 1 Status Channel 2 Status Diagnostic Compatibility Ethernet Version 2 0 IEEE 802 3 D6600 Power Requirements 9 to 30 VDC or 9 to 25 VAC External adapter included Power Consumption 3 W AC Current Required UPS Standby Current 35 mA Power Input AC nominal operating range 120 or 240 VAC AC maximum operating range 100 to ...

Page 3: ...nstalling the D6680 in the AE1 or AE2 enclosure the correct mounting holes must be found on the back wall of the enclosure Only these holes line up correctly to allow the D6680 to be secured with two screws Once the holes are found proceed to mount the D6680 1 Place the D6680 against the back wall of the enclosure 2 Line up the side mounting holes on the D6680 with the enclosure mounting holes ind...

Page 4: ... cover plate using the 6 machine screws nuts and lockwashers provided Mount the cover plate to the gang box with the 10 screws provided with the gang box 6 Energize the power to the circuit s and using a voltmeter test the duplex outlet for proper voltage 7 Punch out a conduit knockout in the low voltage side of the gang box Bring the low voltage wiring through the knockout hole and into the gang ...

Reviews: