Initial settings
TIME of DAY
-
This can be adjusted in the settings area of the web interface and displays in
12:00 or 24:00 format.
SWING
-
This can be set in the settings area of the web interface.
SWING controls how frequently your HVAC comes on. This feature allows you to set the desired
variance in temperature between the CT110 setting and the room temperature required before
the heating or cooling system will turn on—Swing range: 0.5 to 2.0°F (.25 to 1°C). For example,
if SWING is set to 2.0°F and the CT110 is set to 70°F Target Temperature, the heat cycle will
start when room temperature drops to 68°F. Similarly, the cooling system will start when the room
temperature increases to 72°F. The HVAC then runs and will shut off at the Target Temperature.
You can set the SWING from 0.5° to 4.0°F (.5 to 2°C). The HVAC will run more frequently at .5°F and
less at 4°F. Default is 1°F.
Differential -
This can be set in the settings area of the web interface. (Used for multiple stage
systems only, not displayed for single stage) The differential is the number of degrees between
the room temperature and the Target Temperature at which the 2nd stage will be used. Default is
2°F , range is 2°F to 6°F (1°- 3°C). Recommend 2°F for very cold climates and the 4°F for warm
climates and 6°F for hot climates.