Table 10 Period Bye (byte 1) from Downlink Configuration Message
Bit 7
Bits 6:0
0
Period defined in hours (1-127 hours)
1
Period defined in minutes (1-127 minutes)
For example, to receive a report every 4 hours, byte 1 would be set to 0x04. To receive a
periodic report every 15 minutes, byte 1 would be set to 0x8f.
Note that
prior to firmware version 1.3, only hourly reporting is available
. The
firmware version can be found in the reset message and is logged on the Radio Bridge
console.
Periodic reporting is not recommended as it will increase data service
fees and significantly reduce battery life. Wherever possible, use
thresholds or report-on-change only.