Radimo RADISTAT MAN User Manual Download Page 2

2

to the new setpoint. Then press the 

TEST

 button on the top of the 

thermostat. The test is successful if the red light in the 

TEST

 button 

lights up and 

GROUND FAULT

 is shown on the display. If this does 

not occur, check the installation/contact your electrical installer. Press 
the 

Standby/Reset

 button to reset the GFCI.

The red light should go out and the display returns to normal ap-
pearance.
Press the 

Down

 button to return to the original temperature setting. If 

the test fails, check the heating cable and thermostat. 
If during normal operation the GFCI trips without the 

TEST

 button 

being pressed, there could be a ground fault! To check whether it 
is a ground fault or nuisance tripping, press 

Standby/Reset

. If this 

and the system is operating correctly. If this does not occur, there is a 
ground fault! Contact your electrical installer.

Settings

The thermostat has an intuitive menu, allowing it to be easily set. 
Press 

OK

 to access the following options: 

RADISTAT MAN 

FLOOR 
TEMP

Displays actual floor 
temperature.

SCALE HIGH Allows you to set the highest temperature 

to which the thermostat can be adjusted. 
Press 

OK

 and change the temperature 

with the 

UP

 or 

DOWN

 button. 

Confirm with 

OK

.

SCALE LOW

Allows you to set the lowest temperature 

to which the thermostat can be adjusted. 
Press 

OK

 and change the temperature 

with the 

UP

 or 

DOWN

 button. 

Confirm with 

OK

.

C ° / F °

Allows °C (Celsius) or °F (Fahrenheit) to 

be selected as the temperature unit.  
Press 

OK

 and change the temperature 

unit with the 

UP

 or 

DOWN

 button. 

Confirm with 

OK

.

OFFSET 
TEMP

between the thermostat and a room ther-
mometer to be set.
Press 

OK

. Press the 

UP

 or 

DOWN

 button 

0.2°F/0.1°C). Confirm with 

OK

APPLICATION

Allows you to select 
FLOOR SENSOR or REGULATOR.
FLOOR SENSOR: A floor sensor is used. 
Only floor temperature is controlled.
REGULATOR: The thermostat functions 
as a simple regulator and no sensors are 
used.
Press 

OK

. Press the 

UP

 or 

DOWN

 button 

to select FLOOR SENSOR or 
REGULATOR. Confirm with 

OK

EXIT

Exits the menu. 
Press 

OK

 to return to the initial display.

Standby

stat and display. 
Press and hold the Standby button for 2 seconds. The display shows 

OFF

To turn the thermostat on again, simply press the Standby button.  

Error messages

E0 = Internal failure. Replace thermostat.
E1 = Internal sensor defective or short-circuited. Replace thermostat.
E2 = External sensor defective or short-circuited.  
 

Check external sensor.