MAINTENANCE INSTRUCTIONS
37
P
ARAMETER
P07
-
M
INIMUM CENTRAL HEATING OUTPUT
12.
Enter the parameters menu and select parameter P07. The
pressure gauge will indicate the gas pressure. If this pressure
value is different to that on the rating plate of the boiler (
see
paragraph
5.4 ‘Gas Data’
)
, use ‘
’ and ‘
’ buttons (D.H.W
temperature setting)
to modify the value of the parameter.
The range of settings is 00 - 80.
13.
Press mode selection button ‘
’ to confirm and to
render the new adjustment operative. The parameter number
(P07) will appear on the display.
14.
Press simultaneously ‘
’ and ‘
buttons until
OFF
appears
on the display.
15
.
Disconnect the pressure gauge from the pressure tale-off point
‘
B
’ on the gas valve and carefully tight the screw making sure
there are no gas leaks.
24
P07