Installation Manual 

 

COMBI  -  TA01A011.B1003 

 

 

5

FLUE POSITION 

 

IMPORTANT:  THE FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN BS 
5440:1. 

The boiler MUST  be installed so that the terminal is exposed to the external air. 

It is important that the position of the terminal allows free passage of air across it at all times. 

If the terminal discharges into a pathway or passageway check that combustion products will not cause nuisance and that the terminal will 
not obstruct the passageway. 

In certain weather conditions a terminal may emit a plume of steam.  Positions where this would cause a nuisance should be avoided. 

IMPORTANT REQUIREMENT:  The correct dimensional relationship between the terminal and any obstruction, openable window or 

ventilator as shown in Fig 1 pag.7 It is ESSENTIAL TO ENSURE,  in practice, that products of combustion discharging from the terminal 
cannot re-enter the building, or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration, or 

forced ventilation/air conditioning systems.  If this should occur, the appliance MUST BE TURNED OFF IMMEDIATELY and the local gas 

region consulted. 

Where the lowest part of the terminal is fitted less than 2m (6.6ft) above a balcony, above ground, or above a flat roof to which people have 

access, the terminal MUST be protected by a purpose designed guard.  
Where the terminal is fitted within 850mm (34in) of a plastic or painted gutter, or 450mm (18in) of painted eaves, an aluminium shield of at 

least 1000 mm (40in)  long should be fitted to the underside of the gutter painted surface. 

The air inlet/products outlet duct and the terminal of the boiler MUST NOT be closer than 25mm (1in) to combustible material.

 

 

 

 

TERMINAL POSITION 

 

J

E

A

G

M

F

F

A

D

H,I

TOP VIEW REAR FLUE

D

G

L

K

G

N

B.C

TERMINAL 
ASSEMBLY

PROPERTY BOUNDARY LINE

300 min

 

 
 

A

  Directly below an openable window, air vent or any other ventilation opening. 

300 mm 

B

  Below gutter, drain pipes or soil pipes. 

25  mm  

C

  Below eaves. 

25  mm  

D

  Below balcony or carport roof. 

25  mm  

E

  From vertical drain pipes or soil pipes. 

25  mm  

F

  From internal or external corners. 

25  mm  

G

  Above adjacent ground, roof or balcony level. 

300  mm  

H

  From a surface facing the terminal. 

600  mm  

I

 

Facing the terminals. 

1200  mm  

J

  From opening (door, window)in the carport into dwelling. 

1200  mm  

K

  Vertically from a terminal on the same wall 

1500  mm  

L

  Horizontally from a terminal on the same wall 

300  mm  

M

  Above an opening, air brick, opening window etc. 

300  mm 

N

  Horizontally to an opening, air brick, opening window etc. 

300  mm 

 

 

 

 

 

Fig. 1 

Summary of Contents for RH 28

Page 1: ...TA01A011 B1003 Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS Model RSF 30 E TYPE C ROOM SEALED SEDBUK BAND D ...

Page 2: ......

Page 3: ...TEM page 3 GENERAL INSTALLATION REQUIREMENTS page 4 BOILER INSTALLATION page 6 ELECTRICAL CONNECTIONS page 8 13 BOILER CONTROL PANEL page 9 STARTING UP THE BOILER FOR THE FIRST TIME page 9 MULTIGAS OPERATION page 11 MAIN COMPONENTS page 12 MAINTENANCE page 15 UNPACKING page 15 SHORT LIST OF COMPONENTS page 16 ...

Page 4: ...sion vessel 2 WARNINGS REGARDING INSTALLATION Warranty expires 12 months from date of installation and in all cases no later than 18 months from date of construction First start up must be performed by authorised personnel only For any operation on the hydraulic gas or electrical circuit regarding the heating unit refer to authorised technicians only and use original spare parts only Wall mounted ...

Page 5: ...774 Heating temperature adjustment C 30 80 Max working pressure heating bar 3 Min working pressure heating bar 0 3 Expansion vessel capacity initial pressure 1 bar Litres 10 Hot water flow rate t 30 Litres 15 24 Max working pressure water bar 6 Min working pressure water bar 0 5 Width mm 450 Height mm 800 Depth mm 320 Weight Kg 49 Coaxial exhaust flue diameter Double exhaust flue diameter Ø Ø 125 ...

Page 6: ...E USE ORIGINAL RADIANT APPROVED FLUE KIT SYSTEMS FLUE ACCESSORIES AND FLUE DIAPHRAGMS ONLY APPROVED RADIANT FLUE DIAPHRAGMS AND ADJUSTMENT TABLES ARE SUPPLIED WITH RADIANT ORIGINAL FLUE KIT SYSTEMS R C G F A 55 5 65 5 77 70 80 102 45 40 60 50 55 1 0 5 50 40 30 80 60 70 1 5 1 5 S TOP ON AUT OF F 9 720 80 85 280 85 82 82 190 35 55 5 120 80 G 65 5 R 77 70 C 50 45 55 40 60 60 50 30 40 80 70 80 F 102 A...

Page 7: ...pework that supplies the boiler must be a 22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the above code BS 6400 1985 BS6891 IMPORTANT BOTH THE USER AND THE MANUFACTURER RELY UPON THE INSTALLER WHOSE JOB IS TO INSTALL THE BOILER AND CONNECT IT TO A CORRECTLY DESIGNED HEATING SYSTEM THE INSTALLER SHOULD...

Page 8: ...ere the lowest part of the terminal is fitted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed guard Where the terminal is fitted within 850mm 34in of a plastic or painted gutter or 450mm 18in of painted eaves an aluminium shield of at least 1000 mm 40in long should be fitted to the underside of th...

Page 9: ...llation the boiler is equipped with a fittings kit see fig 3 IMPORTANT Before connecting the heating system pipes carefully clean the system to prevent residual dirt from entering into circulation and negatively affecting boiler function Install a funnel with discharge under the safety valve calibrated to 3 bar to collect water in case of leaking due to overpressure No safety valve is needed for t...

Page 10: ... with an Anti Freeze system which comes into operation when the temperature falls to 5 C Heating sensor and 4 C Hot water sensor and protects the boiler down to 10 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost system will only come into operation if the boiler is filled with water and connected to a live gas supply with e...

Page 11: ...nstrument panel as follows A Turn off the electrical power supply at the mains B Remove the boiler front casing C Undo the two screws on the panel and turn it to the position shown in fig 1 pos 1 D After pulling the panel downwards undo the screws on the housing and open the small rear panel plate as shown in the figure 1 E With the electrical box now open make the following connections Connect th...

Page 12: ...eutral and earth connections have been properly connected make sure the type of gas being supplied is the same as the type for which the boiler has been tested and approved see plate data make sure the unit is properly earthed make sure there are no flammable liquids or materials in the immediate vicinity of the boiler make sure that any shut off valves in the heating circuit are open open the gas...

Page 13: ...ON position and try the ignition procedure once again If the boiler does not start reset boiler and Set the ON OFF switch 1 to OFF and then ON position IMPORTANT should the boiler fail to ignite wait 3 minutes before a new ignition procedure In case of water deficiency the display shows code 04 intermittent and the Led 8 is ON To restore water pressure open the tap on the filling loop and fill the...

Page 14: ...ed d calibrate the new max and min settings for the modulator e replace the gas setting plate that indicates the type of gas and nominal pressure for the boiler When converting the boiler to work with a different type of gas remove the existing plate and replace it with the new one supplied in the conversion kit GAS DATA TABLE Models RSF 30 E NATURAL GAS G 20 LIQUID BUTAN GAS G 30 LIQUID PROPANE G...

Page 15: ...TY THERMOSTAT 9 ELECTRONIC GAS VALVE VK4105 10 ELECTRONIC IGNITION BOARD 11 EXPANSION VESSEL 12 3 SPEED CIRCULATION PUMP WITH AIR VENT 13 AUTOMATIC AIR VENT 14 HEATING CIRCUIT 3 bar PRESSURE RELIEF VALVE 15 WATER PRESSURE GAUGE 16 WATER PRESSURE SWITCH 17 HEATING SENSOR 18 HOT WATER SENSOR 19 3 WAY DIVERTER VALVE 20 FLOWSWITCH CONNECTION WITH FLOW LIMITER 21 ELECTRONIC FLOWSWITCH 22 BY PASS 23 AIR...

Page 16: ...NC M1 1 2 3 4 brown light blue IG black black 17 1 PWM 12 light blue 10 11 grey black RS light blue brown 13 14 16 15 L 12 11 9 10 8 7 6 5 4 3 2 N 56 1bar PAC brown black M3 55 brown brown light blue black 59 57 58 60 61 PWM CONNECTOR FOR SM6545QM 1012 EA ER EV VD FAN black black M10 52 51 53 54 Optional TERMINAL BLOCK M9 L 50 Hz N 230V TA SE DISPLAY DIGITAL BOARD 2000 SKO6206 COD 76654LA SAFETY T...

Page 17: ...ction can be made to either the remote control fig 5 or to the terminal block fig 3 dotted line on the terminals marked SE SE WARNING The remote control connection cable must pass through a channel which is separate from any system supplied with power If this is not possible fit a screened cable M6 M4 M3 M5 M2 M1 M4 M13 M7 M11 M8 M12 M10 M9 EXTERNAL SENSOR 2 M1 1 TEL S EXT IN REMOTO N L Se TA TA S...

Page 18: ...modulation Check that the electrical connection conforms to the description in the instruction manual for the boiler Check the domestic hot water flow rate and temperature When dismantling the boiler casing removing as shown in fig 1 UNPACKING A Set the packed boiler fig 2 down on the floor making sure that the arrow is pointing upwards and remove the sticking tape Open the 4 flaps outwards B Turn...

Page 19: ...N 230V ES 30 108 G 00 0416 9 43157LP SEALING CLIPS KIT FOR MULTIPLEX GROUP 9 58009LP MAIN HEAT EXCHANGER mod 30 000 kCal h 9 59012LP AIR PRESSURE SWITCH CE C6065FH1748B 9 59015LA WATER PRESSURE SWITCH 1 8 PC 5411 9 73507LA HEATING 1 8 SENSOR 9 73508LA D H WATER 1 8 SENSOR 9 76631LA ELECTRONIC IGNITION BOARD CVI S4565 A 2019B 9 76654LA DISPLAY DIGITAL BOARD 2000 SKO6206 9 76655LA PRINTED CIRCUIT BO...

Page 20: ...FLET HAVE BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET E OE ALL RIGHTS RESERVED NO PART OF THIS DOCUMENT MAY BE REPRODUCED SAVED IN STORAGE SYSTEMS OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WHETHER ELECTRONIC MECHANICAL PHOTOCOPYING RECORDING OR OTHERS WITHOUT THE MANU...

Reviews: