background image

43

R1BK_50-RAD-ING-Manuale-1812.1_SK.3

2 Av

ver

ten

ze gen

er

ali p

er

 la m

anu

ten

zio

ne

_s

olo

 risc

_co

nd

_E

N

2 Av

ver

ten

ze gen

er

ali p

er

 la m

anu

ten

zio

ne

_s

olo

 risc

_co

nd

_E

N

2.    MAINTENANCE

SUPPOR

T CENTRE

2.2. MAINTENANCE

2.2.7. GENERAL MAINTENANCE 

WARNINGS

 DANGER

Before each components cleaning or 

replacement operation, ALWAYS cut off the POWER, 
WATER and GAS supply of the boiler.

 WARNING

To ensure greater life span and proper 

operation of the device, during the maintenance 
operations use only original spare parts.

 ATTENTION

To ensure the efficiency and safety of the 

device, the maintenance operations must be realized 
on an annual basis. The operations described below, 
are essential to the validity of the standard RADIANT 
warranty and must be performed by professionally 
qualified personnel in accordance with current 
legislation and authorized by RADIANT.

Please perform the following operations once a year:

 › Check that the system’s water PH is between 7 and 

8.5;

 › check the sealing of the gas components, and 

replace if necessary the gaskets;

 › check the sealing of the water components, and 

replace if necessary the gaskets;

 › visually check the flame and the condition of the 

combustion chamber;

 › if necessary make sure that the combustion 

is suitably adjusted and if required proceed as 
indicated in section “CO2 VALUE CHECK AND 
CALIBRATION”;

 › remove and clean the burner from oxidation;

 › check the integrity and the position of the sealed 

chamber sealing gasket; 

 › check the primary exchanger, if necessary, clean 

it;

 › check the operation of the gas light up and safety 

systems. If necessary, remove and clean the 
flame detection and light up electrodes from 
incrustations paying attention to respect the 
distances with respect to the burner;

 › check the heating circuit safety systems: limit 

temperature safety thermostat; limit pressure 
safety;

 › check the pre-load pressure of the expansion 

vessel;

 › make sure that the permanent ventilation outlets 

are present, correctly sized and functioning, based 
on the installed devices. Respect the requirements 
provided by Local and National legislation;

 › periodically check the integrity of the fume 

exhaustion system for safety and proper operation;

 › check that the wiring is performed in compliance 

with the requirements in the boiler instruction 
manual;

 › check the wiring inside the control panel;

 › check the proper operation of the condensate 

draining system, including the devices outside 
the boiler such as condensate collection devices 
installed along the path of the fume exhaust duct 
or neutralization devices for acid condensate.

 › check that the liquid flow is not obstructed and that 

there are no combustion gas refluxes inside the 
internal system.

Summary of Contents for R1BK 50

Page 1: ...R1BK_50 RAD ING Manuale 1812 1_SK 3 Installation Use and Maintenance Manual for model 0476 R1BK 50 Floor standing premix condensing system boiler for outdoor installation...

Page 2: ...ION 22 1 1 14 ELECTRICAL CONNECTION 22 1 1 15 POWER SUPPLY 23 1 1 16 OPTIONAL ELECTRICAL CONNECTIONS INDIVIDUAL INSTALLATION 24 1 1 17 FUME EXHAUST FITTINGS 26 1 1 18 TYPES OF FUME EXHAUST SYSTEMS 27...

Page 3: ...56 2 2 18 GAS CONVERSION 57 3 USER SECTION 59 3 1 USE 60 3 1 1 GENERAL USE WARNINGS 60 3 1 2 CONTROL PANEL 61 3 1 3 DISPLAY ICONS 62 3 1 4 INFO MENU DISPLAY DATA 63 3 1 5 START UP 64 3 1 6 OPERATING...

Page 4: ...itles are differentiated by thickness and size in accordance with their hierarchy The images contain important parts described in the text marked with numbers or letters See chap chapter name this ent...

Page 5: ...n without any obligation to third parties neither will the company be held responsible for any inaccuracies in this handbook deriving from printing or translation errors the material and intellectual...

Page 6: ......

Page 7: ...ified personnel having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants as pr...

Page 8: ...t The air vent must be placed at floor level to prevent it from being obstructed protected by a grid that does not hamper the useful section of passage The device is suitable for use with the type of...

Page 9: ...tances kit see chapter ANTI FREEZE PROTECTION WARNING The manufacturer will not be held responsible for damages caused by incorrect installation not in conformity with the over mentioned instructions...

Page 10: ...packing elements cardboard box woodencrate nails fasteners plasticbags expanded polystyrene etc must be kept out of the reach of children as they may be dangerous Therefore they should be dismantled s...

Page 11: ...gombro_R1BK 50_SK 2_EN 1 INSTALLATION 1 1 5 OVERALL DIMENSIONS LEFT SIDE AI HEATING FLOW 1 1 2 RI HEATING RETURN 1 1 2 G GAS 3 4 SC CONDENSATE DRAIN 25 E CABLE GLANDS 20 S FLUE OUTLET 80 130 582 280 2...

Page 12: ...nsioni di ingombro_R1BK 50_SK 2_EN 1 INSTALLATION RIGHT SIDE AI HEATING FLOW 1 1 2 RI HEATING RETURN 1 1 2 G GAS 3 4 SC CONDENSATE DRAIN 25 E CABLE GLANDS 20 S FLUE OUTLET 80 130 582 280 264 270 354 S...

Page 13: ...RA RS 15 7 5 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 0 0 2 0 4 0 6 0 8 1 0 2 0 4 6 8 10 12 14 0 1 2 3 4 5 6 7 8 0 10 20 30 40 50 60 70 80 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 0 0 20 40 60 3780 25PWM1 4270 15PWM1...

Page 14: ...nance operations you have to respect the minimum technical spaces indicated in figure 1 ATTENTION In boiler installation follow the instructions given for installation Incorrect slopes of the device w...

Page 15: ...n The manufacturer is not responsible for any flooding due to the opening of the safety valve in case of system overpressure WARNING On systems with a closed expansion tank the pressure reducer on the...

Page 16: ...ty water adding a detergent when it is suspected that the system might be dirty or particularly clogged and at the next loading with new treated water Water treatment In order to preserve the integrit...

Page 17: ...nd make up water of the system if it does not fall under the values indicated below should be softened Moreover additives can be added in order to maintain the limestone into the solution The hardness...

Page 18: ...en the cap of the jolly valve placed on the top of the condensing block to release the air form the top of the system 1 fig 1 2 check that the jolly valves vent the air present in the system are not b...

Page 19: ...RAIN The heat generator produces a significant quantity of condensate during operation This condensate hasanacidpHof3 5 Observethenationalstandard in force and the local regulations for the disposal o...

Page 20: ...The acidity of the condensate can be checked by using litmus paper in order to determine the pH Then the neutralised condensate can be transported into the sewage system MAINTENANCE The pH parameters...

Page 21: ...heating flow water temperature reaches the 30 C and in presence of a return sensor until the heating return water temperature reaches the 20 C The system starts even if on the display appears OFF as...

Page 22: ...te 1 1 14 ELECTRICAL CONNECTION DANGER The equipment is electrically safe only if it is properly connected to an efficient grounding system performed in compliance with the safety standards in force Y...

Page 23: ...f the voltage from the main switch remove the boiler s front casing refer to chapter ACCESSING THE BOILER access the terminal box of the electrical connection box and proceed with the electrical conne...

Page 24: ...ACCESSING THE BOILER unscrew the screws and remove plate A see fig 1 After removing the plate connect the electrical cables to terminal B see fig 1 For the external temperature Probe connect the two n...

Page 25: ...e crankcase connect the items below to the electronic board see fig 1 After performing these operations remount the crankcase and the front casing TP CT BUS 0 10V GND BUS 11 10 9 8 7 12 13 14 15 16 17...

Page 26: ...ndensate draining points connected to the siphon in order to avoid that the condensate produced in the chimney goes into the generators For all discharge ducts with regard to the fumes path you should...

Page 27: ...rge directly from roof and draws air from atmosphere Please see the maximum discharge length in the table in chapter technical data The maximum discharge and intake length or linear reference length c...

Page 28: ......

Page 29: ...SECTION All operations described below relative to first start up maintenance and replacement should be performed only by qualified personnel as provided by standards and regulations in forced 2 SUPPO...

Page 30: ...ke sure that the grounding system works properly make sure that the combustion air adduction and fumes and condensate discharge take place properly in compliance with the Local and National Laws and S...

Page 31: ...the circulating pump automatic reset again further 3 minutes and switch off the power supply and switch it on again Open the gas tap Use the button to select the desired operation mode If the symbol...

Page 32: ...screw 2 fig 2 of the Off Set adjuster To increase the CO2 value turn the screw clockwise and vice versa if you want to decrease it Once completed the adjustment tighten the protection screw A fig 2 o...

Page 33: ...ING THE PARAMETERS To access the parameters menu and adjust their values follow the procedure below 1 Press the button to select the OFF mode displayed using the symbol 2 Hold at the same time the key...

Page 34: ...RT CENTRE 4 Use the keys and of the symbol to change the value of the parameter 5 Press the key to confirm the action and wait for the display to stop blinking indication of the fact that the adjustme...

Page 35: ...LER MODEL SELECTION 0 10 0 13 KW 1 18 KW HEAT 24 KW DOMESTIC 2 25 KW 3 28 KW 4 34 KW 5 55 KW 6 100 KW 7 R1K 18_24 R2K 24 R2KA 24 IN ALL VERSIONS 8 R1K 25_28 R2K 28 R2KA 28 IN ALL VERSIONS 9 R1K 34 R2K...

Page 36: ...SET THE TIME DURING START UP PHASE NECESSARY FOR THE BOILER TO REACH THE MAXIMUM SET POWER ON THE HEATING SIDE 0 4 0 DISABLED 1 50 SECONDS SET BY DEFAULT 2 100 SECONDS 3 200 SECONDS 4 400 SECONDS P05...

Page 37: ...G A REQUEST TO OPERATE IN DOMESTIC MODE THE VALUE IS PRE SET BASED ON THE SET POWER SEE PARAMETER P00 AND ON THE GAS TYPE SEE PARAMETER P02 45 VALUE SET FOR PARAMETER P11 THE VALUE IS EXPRESSED IN HER...

Page 38: ...STMENT THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED DURING START UP THE VALUE IS PRE SET BASED ON THE SET POWER SEE PARAMETER P00 AND ON THE GAS TYPE SEE PARAMETER P02 VALUE SET FOR PARAMETER P10...

Page 39: ...5 C THE SYSTEM TYPE CAN BE SET FROM PARAMETER P03 0 30 SET BY DEFAULT AT 25 THE NUMBERING OF THE VALUE CORRESPONDS TO KD CURVES ON THE CHART SEE CHART BELOW P17 DISABLEMENT OF DOMESTIC HOT WATER LINE...

Page 40: ...RATURE 45 75 THE VALUE IS EXPRESSED IN C P22 SET POINT T DELIVERY RETURN ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED THROUGH THIS PARAMETER YOU CAN SET THE TEMPERATURE DIFFERENCE BETWEEN DELI...

Page 41: ...ULT P29 T HEATING POSTCIRCULATION THROUGH THIS PARAMETER IT IS POSSIBLE TO SET THE TEMPERATURE DIFFERENCE FROM THE MAIN BURNER SHUTOFF FOR THE INTERVENTION OF THE ROOM THERMOSTAT TO THE DISABLING OF T...

Page 42: ...UPPORT CENTRE 2 1 6 ELECTRIC FAN FREQUENCY HEAT CAPACITY DIAGRAM GAS TYPE MINIMUM FREQUENCY DURING HEATING MAXIMUM FREQUENCY DURING HEATING G20 Hz 45 247 G30 Hz 45 225 G31 Hz 45 240 G30 G20 G31 0 5 10...

Page 43: ...proceed as indicated in section CO2 VALUE CHECK AND CALIBRATION remove and clean the burner from oxidation check the integrity and the position of the sealed chamber sealing gasket check the primary...

Page 44: ...rner on minimum load 2 Flue efficiency losses with burner off 0 02 Casing efficiency losses full load 0 47 Casing efficiency losses minimum load 1 49 Casing efficiency losses with burner off 0 03 Fume...

Page 45: ...5 90 flue bend mm 1 1 2 Max discharge length 80 Horiz Vertical single pipe m 25 Linear length loss for the add ition of one 45 90 flue bend mm 1 1 2 5 Electrical specifications Voltage frequency V Hz...

Page 46: ...d elmax kW 0 04 At part load elmin kW 0 02 In standby mode PSB kW 0 004 Seasonal space heating energy efficiency s 93 Seasonal space heating energy efficiency class A For boiler space heaters and boil...

Page 47: ...4 START UP TRANSFORMER 15 PROPORTIONAL VENTURI 16 WATER PRESSURE SWITCH 17 CONDENSATE COLLECTION SIPHON 18 STRAINER 19 SYSTEM DRAIN VALVE 20 HYDRAULIC SEPARATOR 21 SAFETY VALVE 22 ISOLATING VALVE 23 I...

Page 48: ...TRANSFORMER 15 PROPORTIONAL VENTURI 16 WATER PRESSURE SWITCH 17 CONDENSATE COLLECTION SIPHON 18 STRAINER 19 SYSTEM DRAIN VALVE 20 HYDRAULIC SEPARATOR 21 SAFETY VALVE 22 ISOLATING VALVE 23 ISOLATING T...

Page 49: ...NT THERMOSTAT AR ORANGE VG GAS VALVE SR HEATING PROBE L LINE GI YELLOW TRA START UP TRANSFORMER EV ELECTRIC FAN N NEUTRAL BI WHITE SRR HEATING RETURN PROBE NE BLACK GR GREY ma ce ma ce ma ce ma gi bi...

Page 50: ...ront of the boiler proceed as follows remove the fastening screws 1 fig 1 placed on the lower edge of the front panel grab the front panel from the bottom and remove it pulling it to yourself A fig 1...

Page 51: ...In order ot intervene on the wirings of the control panel please proceed as follows DANGER Cut off the voltage from the main switch Grab at the same time the support brackets of the control panel fig...

Page 52: ...e system proceed as follows switch the boiler to WINTER mode and activate it turn off the main power supply switch wait for the boiler to cool down connect a flexible tube to the system emptying outle...

Page 53: ...PRESS THE RESET KEY GAS MISSING CHECK THE ADDUCTION NETWORK MASS OR BROKEN START UP ELECTRODE REPLACE IT GAS VALVE BROKEN REPLACE IT SLOW LIGHT UP TOO LOW ADJUSTMENT ADJUST MINIMUM OR SLOW LIGHT UP V...

Page 54: ...ING WATER PRESSURE SWITCH BROKEN REPLACE IT E05 HEATING PROBE BROKEN OR INCORRECTLY CALIBRATED PROBE RESISTANCE VALUE 10 KOHM AT 25 C NTC REPLACE IT AUTOMATIC DISCONNECTED OR WET PROBE CONNECTOR CHECK...

Page 55: ...OMPATIBLE WITH THE P C B REPLACE IT WITH A COMPATIBLE ONE AUTOMATIC E32 COMMUNICATION ERROR BETWEEN THE BOILER BOARD AND THE MODBUS BOARD NO ELECTRICAL CONNECTION CHECK THE WIRING AUTOMATIC MODBUS BOA...

Page 56: ...CTIVATES AUTOMATICALLY WHEN THE HEATING PROBE DETECTS A TEMPERATURE OF 12 C THE BOILER OPERATES AT MINIMUM GAS PRESSURE WITH THE DIVERTER VALVE SET TO WINTER MODE IT DEACTIVATES WHEN THE HEATING FLOW...

Page 57: ...pressure on the rear side of venturi C fig 3 replace the body venturi with the one suitable for the type of supply gas cod 30 00225 for Natural gas cod 30 00226 for Universal LPG and make sure the too...

Page 58: ......

Page 59: ...nd accessed only by qualified operators that fully read and understood the User section paying particular attention to the warnings To ensure the safety efficiency reliability and performances of the...

Page 60: ...due to incorrect use DANGER The boiler should not be used by persons including children with reduced physical sensory or mental capacities or without suitable knowledge or experience unless they are...

Page 61: ...RES AND OTHER INFORMATION see chapter INFO MENU DISPLAY HOLD FOR 5 SECONDS IN OFF OPERATING MODE TO VIEW THE LAST 5 FAULTS 3 OPERATING MODE SELECTION KEY ONLY HEATING OFF 4 RESET KEY FAULTS RESET CHIM...

Page 62: ...TEMPERATURE DISPLAY d7 6 EXTERNAL PROBE INSTALLED EXTERNAL PROBE TEMPERATURE d1 7 TEMPERATURE DISPLAY SET POINT PARAMETER VALUE 8 OPEN THERM COMMUNICATION PRESENT REMOTE CONTROL AREA CONTROL UNIT 9 I...

Page 63: ...RATURE IF AREA BOARD INSTALLED d4 RETURN PROBE TEMPERATURE d5 SOLAR COLLECTOR TEMPERATURE IF SOLAR BOARD INSTALLED SCS d6 SOLAR BOILER TEMPERATURE BOTTOM IF SOLAR BOARD INSTALLED SBSI d7 SOLAR BOILER...

Page 64: ...TEMPERATURE You can adjust the temperature using keys and of the heating circuit press key to decrease the temperature press key to increase the temperature The heating temperature adjustment field ra...

Page 65: ...IONAL NOTE ON ANTI FREEZE FUNCTION The boiler is protected against freezing thanks to the electronic board preparation with functions that start the burner and heat the concerned parts when their temp...

Page 66: ...CAL SUPPORT CENTRE E02 SAFETY THERMOSTAT 95 C CONTACT THE TECHNICAL SUPPORT CENTRE E03 FUMES SAFETY THERMOFUSE 102 C CONTACT THE TECHNICAL SUPPORT CENTRE E04 WATER MISSING IN THE SYSTEM IF THE SYSTEM...

Page 67: ...CT THE TECHNICAL SUPPORT CENTRE E31 INCOMPATIBLE REMOTE CONTROL CONTACT THE TECHNICAL SUPPORT CENTRE E32 COMMUNICATION ERROR BETWEEN THE BOILER BOARD AND THE MODBUS BOARD CONTACT THE TECHNICAL SUPPORT...

Page 68: ...ttive_solo risc_MIAH4_EN 3 USE USER 3 1 9 ACTIVE FUNCTIONS SIGNALLING CODES CODE FUNCTION INTERVENTION F08 H E A T I N G A N T I F R E E Z E FUNCTION ACTIVE WAIT UNTIL THE OPERATION IS COMPLETED F33 S...

Page 69: ...device using a wet cloth and come neutral soap WARNING DONOTuseabrasiveorpowderdetergents as they might damage the plastic cover and control elements 3 1 12 DISPOSAL The boiler and all its accessories...

Page 70: ...RADIANT BRUCIATORI s p a Via Pantanelli 164 166 61025 Loc Montelabbate PU Tel 39 0721 9079 1 fax 39 0721 9079299 e mail info radiant Internet http www radiant it...

Reviews: