4
INSTALLATION
INSTALLATION :
CLEARANCES :
SERVICE CLEARANCES :
The installation must conform with local codes, or in the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.1/NFPA54, or the Natural Gas and propane Installation Code, CSA B149.1, as
applicable, including:
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of ½ psi.
2. The appliance must be isolated from the gas supply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than ½ psi.
A manual shutoff valve (to be supplied by user) must be
installed in the gas supply line upstream of the
appliance and gas pressure regulator (supplied with your
appliance) in the supply gas line for safety and ease
of future service or repair. Your equipment operates at 5
inches water column pressure on natural gas
(Regulator supplied with your appliance) and at 10 inches
water column on propane gas (regulator supplied
with your appliance).
NOTE
: Ensure the gas supply, gas type, as shown on rating plate agree
(rating plate is located on the backside of the front panel of unit)
Pipe gas supply to unit
Back
Sides
Back
Sides
TAHP
Model Series
Combustible
Non-Combustible
TARB
TAMG
TASP
TAWR
12”
8”
7”
17”
17”
12”
8”
8”
17”
15”
0”
0”
0”
0”
0”
0”
0”
0”
0”
0”
For installation on a non‐combustible floor (counter top) only.