A P P E N D I C E S
120
Series 8000™ O&M Manual
Appendix 9:
Setup: V1000 Motor Drives
This process is used to
…
•
reset the Yaskawa V1000 motor drives
•
set up and auto-tune the motors for the electro-mechanical
characteristics of the motors and load
•
set parameters for proper operation in a Model 8200
™
ACU
Caution:
This procedure assumes the motors are not yet in-
stalled on jacks.
It requires them to be able to turn freely.
A-9.1
Reset the V1000
1.
Set A1-03 to 2220, then press Enter to reset the drive.
2.
Set A1-2 to 2 to set the inverter to Open Loop Vector control.
A-9.2
Run the Motor Tuning
1.
Go to ATUN and set the following. (
Note:
example values,
shown in
gray
, probably will not match your specific motors.)
T1-01:
00
Set inverters for rotational auto-tuning.
T1-02:
.19
Motor Rated Power: use the rated power
from motor nameplate, in KW.
T1-03:
230
Motor Rated Voltage: use the rated volt-
age from motor nameplate, in Volts.
T1-04:
1.1
Motor Rated Current: use the rated cur-
rent from motor nameplate, in Amperes.
T1-05:
60
Motor Rate Frequency: use the rated fre-
quency from motor nameplate, in Hertz.
T1-06:
4
Number of Poles: use the number of
poles from the motor nameplate.
Reference
The parameter list
starts on page 176 of
the
V1000 Quick Start
Guide
, included with
the Radeus Labs mod-
el 8250 Drive Cabinet.
The full document is
downloadable.
Note
Experienced, knowl-
edgeable installers
may choose to deviate
from recommended
settings.