same as when setting a physical address. Refer to the Catalyst
manual for that
process.
6. At this point the Catalyst is fully configured to send an alarm on channel 56 if
communication between the PLC and Catalyst is lost.
Let’s also set a general alarm, for this example on Channel 5, SNA 1*2*00003.
Simply change the
Channel Number
and the SNA to the new values and
Click
Change Mode
. The Catalyst
will save and update the settings immediately.
NOTE:
Since the Discrete SNA 1*2*00003 uses one of the bits in the 16bit
Analog register at SNA 1*2*40001, that register cannot be used to store analog
data. Refer to
Section C: SNA Discrete and Analog Register Addressing
for
more information.
7. Repeat these steps to add additional alarms. When you have finished adding
alarms,
Click
Close
to exit the Channel Settings window.
Assign and Configure an Analog Channel
1. From the PC’s
Start Menu
, start
Alarmware v2.0
and connect to the attached
Catalyst
.
2. In Alarmware,
Click
on
Configuration
>
Channels
, Enter the desired
Channel
number
and a
SNA
in the 4xxxx range (Ch. 2 and 1*2*40005 in this example)