0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 
60 Hz. For 0-10 Dimming, follow the wiring directions as shown in 

Fig. 7.

1.  Connect the black/brown fixture lead to the LINE supply lead.
2.  Connect the white/blue fixture lead to the COMMON supply 

lead.

3.  Connect the green/yellow wire from fixture to supply ground. 

Do NOT connect the GROUND of the dimming fixture to 

 

the output.

4.  Connect the purple fixture lead to the DIM V+ lead.
5.  Connect the pink/gray fixture lead to the DIM V- lead.

6.  Cap the yellow fixture lead, if present. Do NOT connect.

TROUBLESHOOTING

1.  Is the fixture grounded properly?
2.  It is recommended that gloves be worn to avoid injury 

 

     during installation.
3. If any smoke or spark, please turn off the power immediately. 

X17 XFU 60-50-30  IN-1021

Note:  

These instructions do not cover all details or variations in equipment nor do they 

provide for every possible situation during installation, operation or maintenance.

P-100056

BLACK/BROWN

LINE

WHITE/BLUE

COMMON

PURPLE

(+) DIM V+

PINK/GRAY

GREEN/YELLOW

(-) DIM V-

GROUND

Fig: 7

FIELD ADJUSTMENT

Follow instructions below to change fixture 

Power

 (

W

) or 

Color 

Temperature

 (

CCT

) from the factory settings and 

Photocell

 On/Off 

option.

Factory Settings: 4000K and 60W

1.  Remove

 Selector Switch Caps 

by turning counterclockwise

 

using a flat head screwdriver 

(Fig. 5).

2.  Locate the 

Selector Switches

 on the fixture 

(Fig. 6).

3.  Select

 Power 

(

W

) and

 Color Temperature 

(

CCT

)

 by sliding the 

respective switch to the desired value.

4.  Select 

Photocell

 On/Off option by sliding respective switch 

 

to the desired value.

5.  Replace 

Selector Switch Caps 

and tighten with a flat head 

screwdriver.

 

5K

4K

3K

3
2
1

Selector Switch Caps

Fig: 5

Fig: 6

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch.  
Do not clean or maintain while fixture is energized.

1.  Clean

 

glass lens 

with non-abrasive glass cleaning solution.

2.  Do not open the fixture to clean the LED. Do not touch the LED.