background image

WIRING

HID ONLY: If supply wires are located within (3) inches 
of ballast, use wire rated for at least 150°C. If supply 
wires are routed and secured min (3) inches away from 
ballast, use wire rated for at least 90° C

.

All QT units are factory wired for 120V except those 
factory ordered with a 277V Photocell (/PC2). If other 
voltages are required, remove refl ector and rewire for 
the appropriate voltage. Do not use any supply voltage 
other than those specifi ed below. 
 
1. Connect the appropriate voltage fi xture lead to the 

HOT supply lead.

2. Connect the “COM” fi xture lead to the COMMON sup-

ply lead.

3. Fixture ground screw must be connected to 

supply ground.

4. All unused leads must be capped and insulated.

WP2C CUT-OFF INSTALLATION INSTRUCTIONS

Thank you for buying RAB Lighting fi xtures. Our goal is to design the best quality products to get the job done right. 
We’d like to hear your comments. Call the Marketing Department at 888-RAB-1000, or email: [email protected]

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.

RAB fi xtures must be wired in accordance with the National Electrical Code and applicable local codes.  
Proper grounding is required for safety. Wallpacks are for outdoor use and should not be used in areas 
with limited ventilation or high-ambient temperatures. Installation should be done by a qualifi ed electrician.

WARNING: Make certain power is OFF before installing or maintaining fi xture.

MOUNTING

Use the

 Drilling Template

 on the inside back 

surface of the housing to match most standard junction 
boxes or lag bolt housing to mounting 
surface using locations noted below.

1.  Open door by loosening (4) screws. Remove 

refl ector.

2.  Prepare the housing for use by drilling out the 

appropriate holes.

3.  Line up the housing in desired location and mount 

securely.

4.  Complete the wiring to the supply wires and ground 

(see wiring instructions).

5.  Replace the refl ector, install the lamp. Close door 

and tighten the four screws.

6.  To insure weatherproof seal make sure all holes 

(mounting, plugs, conduit, etc.) are sealed with 
weatherproof silicone sealant.

LOCATION

Fixture should be located on wall atleast 18” 
below any overhand or other structural detail. Fixture 
should not be recessed. Fixture must be positioned with 
lamp in horizontal position. Housing must be mounted 
on wall with lens facing down as shown in line drawing 
above.

Drilling Template

Lag Bolt Locations

Reviews: