WP1FC Full Cut-off INSTALLATION INSTRUCTIONS

Thank you for buying RAB Lighting fixtures. Our goal is to design the best quality products to get the job done right.  

We’d like to hear your comments. Call the Marketing Department at 888-RAB-1000, or email: [email protected]

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.

RAB Wallpacks must be wired in accordance with the National Electrical Code and applicable local codes.  

Proper grounding is required for safety. Wallpacks are for outdoor use and should not be used in areas  

with limited ventilation or high-ambient temperatures. Installation should be done by a qualified electrician. 

WARNING: 

Make certain power is OFF before installing or maintaining fixture.

LOCATION

Mount fixture on a wall with lens facing down as shown in drawing above. Fixture must be level. Lamp must 

be in a horizontal position. DO NOT mount in a way that would entrap heat.

  

MOUNTING

Use the knockout template on the inside back surface of the housing to match most standard junction boxes 

(see “A”) or for more secure installation, lag bolt housing to mounting surface using points “B”.
1.  Remove the door and reflector
2.  Prepare the housing for use by knocking out the appropriate holes
3.  Line up the housing in desired location and mount securely
4.  Complete the wiring to the power source and ground  

 

(see wiring instructions)

5.  Replace the reflector, install the lamp and mount the door
6.  To insure weatherproof seal make sure all holes (mounting,  

 

plugs, conduit, etc.) are sealed with weatherproof silicone sealant

WIRING

If supply wires are located within (3) inches of ballast, use wire rated for at least 125°C. If supply wires are routed 
and secured min (3) inches away from ballast, use wire rated for at least 90° C.

1. Connect the appropriate voltage fixture lead to the HOT supply lead
2. Connect the “COM” fixture lead to the COMMON supply lead
3. Fixture ground screw must be connected to supply ground
4. All unused leads must be capped and insulated

���

������

�����

���������

��������

������