background image

INSTRUCTIONS

FIELD-ADJUSTABLE SR™ INSTALLATION

RAB Lighting is committed to creating high-quality, aff ordable, well-designed and energy-effi  cient LED lighting and controls that make it easy for electricians to install

and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]

SR - IN - 0922

RAB WARRANTY:

 RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty 

Easy Answers

rablighting.com

Visit our website for product info

Tech Help Line

Call our experts: 888 722-1000

e-mail

Answered promptly - [email protected]

Free Lighting Layouts

Answered online or by request

© 2022 RAB LIGHTING Inc.

P-100266

PINK 

LIGHT

FIXTURE

Vaux 12V

YELLOW

GROUND

GROUND

( - ) DIM V

( + ) DIM V

COMMON

LINE

BLACK

WHITE

PURPLE

Fig. 12

FIELD ADJUSTMENT

Follow instructions below to change the 

Fixture Power

(W)

 and/or 

Color Temperature

(CCT)

from factory settings:

Factory Settings:

SR2  19/14/10W               19W / 4000K
SR4  40/30/20W                40W / 4000K 
SR8  60/50/40W                60W / 4000K  

1. 

Locate the 

Field Adjustable Switches

 on the side of 

Fixture 

Housing 

as shown in Fig. 10.

2. 

Select

 Power 

(W) and 

Color Temperature 

(CCT) 

by sliding 

respective switch to the desired value

(Fig. 10).

40W

30W 2

0W

5000K

4000K

3500K

Follow instructions below to change the Fixture Power (W) and/or Color Temperature 

Power 

(W)

Color Temperature                    

(CCT)

Fig: 10

PIR MODELS

Screw

 Sensor Head

 onto the

 Bracket

 as shown in Fig. 11. See factory 

settings below 

(optional remote sold separately for custom settings,  

CAT# MSR1).

Factory Settings:

• 

Brightness:  100%

• 

Hold Time:   1 Minute

• 

Daylight:       Disabled

• 

Sensitivity:    100%

Bracket

Sensor Head

0-10V DIMMABLE WIRING

RISK OF FIRE. 

Universal voltage driver permits operation at 120V 

through 277V, 50 or 60 Hz. For 0-10V dimming follow the wiring 
directions as shown in Fig. 12.
1.  Connect the black fi xture lead to the LINE supply lead.

2. 

Connect the white fi xture lead to the COMMON supply lead.

3.  Connect the green GROUND wire from fi xture to supply ground.

4. 

Connect the purple fi xture lead to the (V+) DIM lead.

5. 

Connect the pink fi xture lead to the (V-) DIM lead.

6. 

Cap the yellow fi xture lead, if present. Do NOT connect. 

SR VHOOK ACCESSORY KIT

SR JOIN Kit includes the following:

• 

Joiner Bracket w/ 8 Screws

• 

Nuts

 (12)

SR JOIN ACCESSORY KIT

TROUBLESHOOTING

1.  Check that the line voltage at the fi xture is correct. Refer to 

wiring diagram.

2. 

Be sure the fi xture is grounded properly.

CLEANING & MAINTENANCE

CAUTION: Be sure fi xture temperature is cool enough to touch. 

Do not clean or maintain while fi xture is energized.

1.  Clean

 polycarbonate 

lens with non-abrasive cleaning solution.

2. 

Do not open the fi xture to clean the LEDs. Do not touch the LEDs.

SR VHOOK Kit includes the following:

• 

40” Chain 

(2) 

• 

V-Hooks

 (2)

• 

Wires 

(12 - Tinned copper)

Fig. 11

Note: 

 These instructions do not cover all details or variations in equipment nor do 

they provide for every possible situation during installation, operation 
or maintenance.

MVS MODELS

(Internal)

• 

Sensitivity:    50%

• 

Stand-by dimming level:  20%

• 

Stand-by time:  1 Minute

(optional remote sold separately for custom settings,  CAT# MSR1).