background image

CONVERTING THE FDV350 DIRECT VENT TO A VENTED FIREPLACE

22

Part # F35BVC

B-VENT CONVERTER INSTRUCTIONS

WARNING: Operation of this appliance when not connected to a properly installed and maintained

venting system or tampering with the blocked vent shutoff system can result in carbon monoxide (CO)

poisoning and possible death.

1.

Place a bead of Black Mil Pac sealant around 4 inch flue collar on the stove.

2.

Position Safety Spill Switch wires to rear of stove and Lower B-Vent Converter onto the 4 and 7 inch collars until
fully seated.  Screw the Converter to the stove with 2 of the 4 screws supplied.

3.

Place the decorative collar around the adapter and screw in place.

4.

Route the Safety Spill Switch wires down the rear of the stove as shown in the above diagram

5.

On the rear of the valve there is a blue wire with male female connecter which must be disconnect by pulling apart
very carefully, connect the spill switch wires to the blue wires on the rear of the valve.

6.

The stove has now been converted to a vented appliance. (FV350)

7.

Place approval label on label plate, over top of FDV350 Rating Plate.  Be sure to line up so serial number of old
unit is legible.

Correct Draw

Incorrect Draw.

Downdraft

occurring

Decorative Band

Decorative Collar screw

Summary of Contents for Kingsman Fireplaces FDV350

Page 1: ...Propane Horizontal installations the venting must be a minimum of one foot vertical off the flue before going horizontal Installation Instructions Model Number FDV350 Free Standing Direct Vent Gas St...

Page 2: ...the installations e g marble tile and the adhesives used to adhere this product to the walls can react with heat and cause odours It is recommended that you burn your gas fireplace or stove for a mini...

Page 3: ...Installation of brick panel kit 12 Log assembly 13 Optional fan kit installation 14 Millivolt system lighting burner control 15 Vent termination 16 General venting information 17 Vent pipe assembly 1...

Page 4: ...ED USING THE B VENT CONVERTER CANNOT BE INSTALLED IN A MANUFACTURED MOBILE HOME Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrica...

Page 5: ...the appliance 15 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent...

Page 6: ...in the living area outside the bedroom s The carbon monoxide detector shall comply with NFPA 720 B A carbon monoxide detector shall be located in the room that houses the appliance or equipment and s...

Page 7: ...l with no additional floor protection being required This unit has been tested in a Alcove the minimum size of Alcove is Depth 30 Height 55 5 Width 52 5 THE FOLLOWING MINIMUM DISTANCES TO COMBUSTIBLES...

Page 8: ...n excess of 1 2 PSIG 3 5 KPa 9 The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at t...

Page 9: ...eries Children and adults should be alerted to the hazards of high surface temperatures of this appliance and should stay away to avoid burns or ignition of clothing Control compartments burners and a...

Page 10: ...er cardboard coal be used in this appliance NOTE it is normal for your gas stove to give off some odour the first time it is burned This is due to the curing of the paint and any undetected oil from t...

Page 11: ...the Door Frame to the unit reverse the above steps GENERAL GLASS INFORMATION GLASS CLEANING It will be necessary to clean the glass periodically During start up condensation which is normal forms on t...

Page 12: ...right of panel tilt the top panel towards you slightly and pull your right hand towards you slightly and place panel onto the rear of the firebox NOTE TAKE CARE NOT TO DAMAGE PILOT ASSEMBLY WHEN PLACI...

Page 13: ...side of the log mounting pan as shown in the picture Fig 5 Log C has to be lowered into position just behind logs A and B Log C has an area notched out of the rear of it to fit over rear positioning b...

Page 14: ...kwise Use the set screw on the side of the variable speed control to increase or decrease the minimum fan speed It may be desirable to lower minimum fan speed to decrease the sound level created by th...

Page 15: ...pilot screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA...

Page 16: ...8 inches 45cm N Clearance to perpendicular wall 24 inches 60 cm Recommended to prevent re circulation of exhaust products For additional requirements check local codes V NOTE Clearances are to the edg...

Page 17: ...fically approved and LABELED for this stove may be used This appliance is also approved for use with Simpson Duravent Direct Vent system Ameri Vent Direct Vent Pipe System ICC Excel Direct Metal Fab S...

Page 18: ...mum stove performance HOW TO USE THE VENT TABLE 1 Determine the height of the system and the number of elbows required 2 Use the Venting Chart to determine the maximum horizontal distance allowed Tota...

Page 19: ...ature sealant MIL PAC SEALANT IS RECOMMENDED to the pipe and secure it with the 4 screws If two pieces of 4 flex pipe are to be joined the joint must be siliconed and secured with four screws Before j...

Page 20: ...only time this may be unavoidable is when installing the vent terminal Note Do not remove or move spacer springs attached to 4 inner flex pipe these must be used to assure an 1 1 4 air gap between 4...

Page 21: ...to the top of the horizontal pipe must be maintained Maximum vertical height of system should not exceed 40 feet Spacer springs to be installed on 4 flex pipe every 3 ft on vertical runs On 45 elbows...

Page 22: ...y seated Screw the Converter to the stove with 2 of the 4 screws supplied 3 Place the decorative collar around the adapter and screw in place 4 Route the Safety Spill Switch wires down the rear of the...

Page 23: ...inch single wall or B Vent liquid fuel gas chimney or Flex Gas Liner may be used to adapt existing chimney or liner to stove When installing with B Vent liquid fuel gas chimney install as per B Vent M...

Page 24: ...Galvanized Pipe 7 Dia x 48 Vertical Installations ZDV4FP8 Flex Pipe 4 Diameter 4 Unexpanded to 8 Expanded ZDV4FP20 Flex Pipe 4 Diameter 10 Unexpanded to 20 Expanded ZDV4FC Flex Connector 4 Diameter ZD...

Page 25: ...0633 1001 P634SI VALVE NOVA NG Hl LO 0820634 1001 P216SI THEMOCOUPLE 290 216 FOR 713 714 TOP CON PILOT 1001 P069SI ELECTRODE CABLE 915 069 FOR 713 714 TOP CON PILOT 1001 P167SI ORIFICE 30 LP 977 167 F...

Page 26: ...itch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Generator may not be Check generator with millivolt meter Take reading at generat...

Page 27: ...s other than in a normal residential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matching or a...

Reviews: