background image

8

 For the filter to be removed, the filter 

element must be saturated with water and all 

internal seals must be wet. DO NOT ATTEMPT 

TO REMOVE A FILTER ELEMENT THAT IS NOT 

WET. Doing so may result in breakage of 

the glass sleeve or lamp, and could result in 

personal injury.  

1.   Disconnect unit from power source.

2.  Run water through the unit to insure that the 

filter is saturated and all seals are wet.

3.  Remove the unit from its wall mount 

(if wall mounted)

4.  Grasp the unit firmly and unscrew the cap by 

turning counterclockwise (Figure 13).

5.  Once the cap is completely unscrewed, use 

the tubing disconnect tool to disconnect the 

outlet tube (Figure 14).

6.  With the outlet tube disconnected, lift the 

cap and filter out of the unit. It is not unusual 

for the O-ring at the bottom of the filter to 

stay on the glass sleeve (Figure 15).

7.  Reach in and remove the lower filter O-ring 

seal as shown (Figure 16).

8. 

Sanitize the unit prior to installing the 

new filter. 

To do this, reinstall the cap 

(without the filter installed), reconnect the 

diverter outlet tubing and replace the 

unit on its mount or stand. Reconnect 

power and run water through the unit 

for approximately 5 minutes. Without a 

filter cartridge in the unit, some ozone 

remains in the outlet water, sanitizing 

the upper portion of the unit and the 

outlet lines.

 DO NOT DRINK water that has been run 

through the unit without a filter.

9.  Disconnect power and remove the cap as in 

steps 3, 4 and 5 above.

10. To insure that the lower filter seal will slide 

easily into the unit, wet the glass sleeve 

(Figure 17).

11. The upper (large) seal fits into the top 

Figure 15—Unscrewing cap 

and removing filter

Figure 16

Removing lower O-ring

Lower O-ring

Figure 13

Disconnecting outlet tube

Figure 14

Disconnecting outlet tube

Summary of Contents for Point-of-Use Drinking Water System

Page 1: ...E N V I R O N M E N TA L I N C Ensuring the Safety of Your Water Point of Use Drinking Water System OWNERS MANUAL...

Page 2: ...ar municipal or well water The patented Sterilight treatment system also provides an environment that is inherently hostile to certain microbiological contaminates Please note the following use restri...

Page 3: ...ustrates all the major components of the system shown with the standard faucet diverter your unit may vary slightly from photo If anything appears to be broken or missing please contact your Steriligh...

Page 4: ...ured to the unit with two semi permanent adhesive pads They can be pried loose by pulling firmly down on the back of the stand or by using a screwdriver or lever to pry the stand from the bottom of th...

Page 5: ...rounding air Locate the unit in an area where the air is breathable and free from dust or fumes The unit MUST be mounted vertically with the filter at the TOP of the unit Figure 7 Mounting Pin Install...

Page 6: ...ed with air and the reconverted ozone The air will appear as tiny bubbles sometimes giving the water an initial cloudy appearance After sitting for a minute or so all of the bubbles will rise to the s...

Page 7: ...er The unit MUST NOT be operated without a filter elementexceptwhensanitizing page8 Replace the filter whenever 1 The filter has been in service six or more months 2 1900 or more liters of water 500 g...

Page 8: ...e filter to stay on the glass sleeve Figure 15 7 Reach in and remove the lower filter O ring seal as shown Figure 16 8 Sanitize the unit prior to installing the new filter To do this reinstall the cap...

Page 9: ...and can adversely affect the safety of water leaving the unit REPLACING THE UV LAMP The Sterilight unit uses a high intensity ozone generating lamp which can be obtained from your Sterilight dealer Fo...

Page 10: ...its wall mounting remove the filter drain the water from the unit Figure 21 and lay it down horizontally 3 Using a Phillips head screwdriver remove the retaining screws on the cover located at the bot...

Page 11: ...embly attached to the sink and partially drains when not in use Tubing not securely connected and or tubing lock ring not secured over tubing fitting O ring on top is not properly seated Filter elemen...

Page 12: ...Quartz Sleeve QS SWM PARTS SERVICE Contact your Sterilight dealer SWM SPECIFICATIONS Power requirements SWM1 115V AC 20 WATTS SWM1 2 220V AC 20 WATTS Flow rate Up to 2 lpm 0 5 gpm Minimum inlet press...

Reviews: