background image

5/8 

www.qundis.com Network 

Node 

WTT16 V22 

CE1N2874en 

 

 

09.09.2009 

State of the 
system  

Display 

Explanation 

Remote  
access 

C

During remote access the symbol ‚ ’ will be displayed. 

Highspeed-
mode 

for example 

M

When all network nodes have switched on their receivers for 
fast data exchange, this will be displayed as two dots in the 
upper part of the LCD. 

Bus-connection 
(from version 
2.2) 

for example 

 

If a connection to a bus is being built up, the number of 
the bus and the primary address of this bus will be 
briefly displayed . 
In the example, network node 03 is connected to M-
BUS 

IrDA-master 
mode (from 
version 2.2) 

This mode is started by pressing the button MODE. (< 
0,5 sec). It indicates readiness to connect additional 
IrDA devices (in IrDA Slave mode). This mode stops 
after 10 sec. 

Add (from 
version 2.2) 

for example 

 

If an unregistered IrDA-capable metering device (e.g. 
WHE467) is connected in IrDA master mode, it can be 
inserted into the network node by pressing the button DIS-
PLAY while ADD is displayed. The last 4 digits of device 
number are indicated. (e.g. 20000123). 
The registration of the device takes place and search mode 
starts.  

Delete (from 
version 2.2) 

for example 

 

If an already registered IrDA-capable metering device is 
connected in IrDA-master mode it can be removed from 
the network node by pressing the button DISPLAY while 
DEL is displayed. The last 4 digits of device number are 
indicated (e.g. 20000123). 
The removal of the device takes place and if necessary 
search mode is stopped. 

Copy (from 
version 2.2) 

for example 

 

 

If a new network node (running in idle mode) is connected in 
IrDA-master mode, it is possible to make a copy of all net-
work data into the new node by pressing the button 
DISPLAY while COPY is displayed. 
Copying lasts up to 20 minutes. At the end "StArt Prot" is 
displayed on LCD of the new network node for 1 hour. After 
mounting the new node the protected mode is also started 
by pressing the DISPLAY button. By this procedure the new 
network node is integrated in network and search mode is 
started automatically. 

 
 

Engineering notes 

For detailed engineering instructions, refer to the Engineering Manual CE1J2870. 

Commissioning the WTX.. 

For mains-powered WTX16.... network nodes, the mains connections are to be made first at 
the selected mounting positions (typically on every second floor, mounting height 

 2 m), if 

required. 

Engineering 

Summary of Contents for WTT16 Series

Page 1: ...de is a component of the Q AMR system It has been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the buil...

Page 2: ...WTX16 GSM and WTX16 IP are able to read M Bus meters according to EN13757 2 3 Technical design The network node consists of the following subassemblies transceiver for Q AMR network memory for 500 met...

Page 3: ...11 Firmware memory covered up 12 IrDA Interface optically The wall mounted section of the network nodes WTT16 contains only the main battery In variant WTT16 232 the RS232 interface is fixed here The...

Page 4: ...n also be started manually with the ACT26 service tool Installa tionsmode2 In installation mode the radio network will be built up automati cally Metering devices that transmit installation telegrams...

Page 5: ...on of the device takes place and search mode starts Delete from version 2 2 for example If an already registered IrDA capable metering device is connected in IrDA master mode it can be removed from th...

Page 6: ...voltage must be in the range from AC 100 to 240 V 50 60 Hz There is no protective earth PE connection Then cable strain relief must be provided by fitting cable ties Once the top section of the WT 16...

Page 7: ...once to start the life expectancy calculation for the new main battery The backup battery MUST NOT be removed simultaneously A fatal loss of data would happen After storing the main battery for longe...

Page 8: ...erating voltage WTT16 DC 3 6 V Lifetime of main battery 5 years Operating voltage WTX16 AC 100 240 V 50 60Hz Rated frequency 868 3 MHz Transmitter power 14 dBm Frequency of transmission 1 Perm ambient...

Reviews: