VACON 100 FAULT CODES 

(ABRIDGED) 

Fault Code 

Fault ID 

Fault Name 

Possible Cause 

How to correct the fault 

Overcurrent 

(hardware fault) 

Current draw is too high a (>4*I H) in the motor 

cable. The possible cause can be one of these: 

a sudden heavy load increase

short circuit in the motor windings

motor is not the correct type

parameter settings are not properly 

made 

Check the VFD loading. Check of the 

motor, check of the cables and 

connections.  

Perform a test run.  

Set the acceleration time longer, if 

required. 

Overcurrent 

(software fault) 

10 

Overvoltage 

(hardware fault) 

The DC-link voltage is higher than the limits. 

Deceleration time id too short

There are high overvoltage spikes in 

the supply

Check the input voltage(s). 

Set the deceleration time longer.  

Activate the overvoltage controller. 

11 

Overvoltage 

(software fault) 

20 

Earth fault 

(hardware fault) 

The VFD has detected that that the sum of the 

motor-phase-current is not zero 

An insulation malfunction in the 

cables or in the motor.

A filter (du/dt, sinus) malfunction

Check the motor cables and the motor. 

Check the filter. 

21 

Earth fault 

(software fault) 

600 

System Fault 

There is no communication between the control 

board and the power. 

Reset the fault and restart the drive. If 

the fault re-occurs again, contact the 

Vacon distributor. 

601 

602 

Defective component operation malfunction 

603 

The voltage of auxiliary power in the power unit 

is too low. 

604 

Output phase voltage does not agree with the 

reference. Feedback fault 

605 

Operation malfunction 

606 

Software of control unit is not compatible with 

software of power unit 

607 

The software version cannot be read. There is no 

software in the power unit. Defective 

component. Operation malfunction (power 

board or measurement board). 

608 

A CPU overload 

609 

Defective component. Operation malfunction 

Reset the fault and power cycle the VFD 

twice. ( power off, power on) 

671697

Summary of Contents for Cheetah C3 CUB

Page 1: ...Operating Maintenance Manual www quintex co uk For systems installed with Vacon 100 Inverters FEB 2016 Cheetah C3 CUB Automatic Catering Ventilation Controls 671697...

Page 2: ...ency Drives Vacon 100 Keypad Navigation and Reset TECHNICAL SECTION Vacon 100 Key Settings 8 10 11 Cheetah Input Output unit Single Phase 230V VFD 12 14 Maintenance 15 Error Codes Cheetah Display 16 V...

Page 3: ...ed to be an autonomous system and the fans are set to ramp down to a pre set minimum speed when there is little or no catering demand In most cases where possible the pre set minimum speed is set to 4...

Page 4: ...led in pairs and span the length of a canopy DISPLAY UNIT The Cheetah Display unit provides an operator interface with the Cheetah system SENSOR PROCESSOR UNIT A Cheetah Sensor Processor is a local HU...

Page 5: ...nd therefore the Cheetah system has electrical power applied to it MAX RATE LED The Max Rate light will be on when the system is running at full speed due to use of the OVERRIDE button ALARM HIGH EXHA...

Page 6: ...current supply fan running speed In more complex system installations multiple Cheetah module and fan s may show on the screen when scrolled The normal operating screen is the DEFAULT screen PRESS SC...

Page 7: ...GHER 50Hz temperature set point 0 0 TMinStpt 2 MIN TEMP SPAN C Setting of the LOWER 0Hz temperature set point TMaxStpt 2 MAX TEMP SPAN C Setting of the HIGHER 50Hz temperature set point 0 0 TMinStpt 3...

Page 8: ...uired to suit the new ventilation unit A VFD mounted to outdoor external exposed plant fans needs to be installed in a draft ventilated cabinet ideally near to the Air Handling Unit that is being cont...

Page 9: ...134 9 6A 4kW MR4 VACON0100 3L 0012 5 BM3L SDC4 WT03 A1134 12 0A 5 5kW MR4 VACON0100 3L 0016 5 BM3L SDC4 WT03 A1134 16 0A 7 5kW MR5 VACON0100 3L 0023 5 BM3L SDC4 WT03 A1134 23 0A 11kW MR5 VACON0100 3L...

Page 10: ...ts resets should not be ignored and should be reported MODIFYING INVERTER PARAMETER SETTINGS SHOULD ONLY BE DONE BY TRAINED PERSONNEL STOP button Vacon 100 keypad navigation buttons OK BACK RESET FUNC...

Page 11: ...has been upgraded to a larger size then a larger rated VFD may also be required Vacon 100 COMMON CHEETAH PARAMETERS PARAMETER DESCRIPTION DEFAULT P1 3 Minimum frequency reference 20 00 Hz P1 4 Maximu...

Page 12: ...and the method of control that is employed The technicians that install or replace speed control devices should refer the operating manual of the controlled device to determine the required terminal c...

Page 13: ...d This input allows the actual return percentage fan running speed be fed back from the controlled device to the Cheetah system The actual running speed feed back should be connected but in rare cases...

Page 14: ...cy Drive Cheetah RED WHITE BLACK BLUE ORANGE YELLOW PURPLE GREY BROWN GREEN 8 9 2 AI1 13 5 4 14 15 16 18 20 GREY PURPLE DIODE V mA 8 DI1 6 24V 18 A0 9 DI2 Vacon 20 COMMON CHEETAH CUB PARAMETERS PARAME...

Page 15: ...tem For optimum system performance it is recommended that the temperature sensors are routinely cleaned every 6 to 12 months depending on cooking activity and the resulting contaminant build up To cle...

Page 16: ...0000000 00010000 32 Hood 1 00000000 00100000 64 Hood 2 00000000 01000000 96 Hoods 1 2 00000000 01100000 128 Hood 3 00000000 10000000 160 Hoods 3 1 00000000 10100000 192 Hoods 3 2 00000000 11000000 224...

Page 17: ...t hardware fault The VFD has detected that that the sum of the motor phase current is not zero An insulation malfunction in the cables or in the motor A filter du dt sinus malfunction Check the motor...

Page 18: ...cable Advanced inspection Check the rectifying bridge and the gate control of the thyristor 11 100 Output phase supervision The VFD has detected that there is no current in 1 motor phase a motor or m...

Page 19: ...ccurs in the VFD frame sizes MR7 or larger Reset the fault and restart the drive Clean or replace the fan 312 Fan cooling The VFD cooling fan has exceeded its operating lifetime 50k hours Replace the...

Page 20: ...e counter is higher than the fault limit 1303 Maintenance counter 2 alarm The value of the maintenance counter is higher than the alarm limit 1304 Maintenance counter 2 fault The value of the maintena...

Page 21: ...TH ONE YEAR WARRANTY FROM THE DATE OF INSTALLATION FOR MANUFACTURE DEFECTS THE VACON FREQUENCY INVERTERS HAVE A 12MONTH ONE YEAR WARRANTY FROM THE DATE OF INSTALLATION MALICIOUS OR ACCIDENTAL DAMAGE O...

Page 22: ...2A input 230V ac Remote Comms Data Logging Unit DIGITAL TEMP SENSOR DUCT MOUNTED OPTIC SENSOR RECEIVER OPTIC SENSOR EMITTER ANALOGUE REF FREQ OUTPUT SIGNAL AVAILABLE FOR BMS VACON INVERTERS MUST BE IN...

Reviews: