Section IX – Technical data
112 Quincy Vacuum Pump-QSV Series
For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
Install the prescribed maximum fuse (150 A) on each cable
Parallel supply cable (2 x 3 2 PE - configuration (2)):
I = (128 A + 25%)/2 = (128 x 1.25)/2 = 80 A
For an AWG4, the maximum current is 85 A x 0.8 = 68 A, which is insufficient. For an AWG3, the
maximum current is 100 x 0.8 = 80 A. So 2 parallel cables of 3 x AWG3 + 2 x AWG8 are sufficient.
Install 80 A fuses on each cable.
9.3 Reference condition and limitations
Reference conditions
Relative humidity
%
0
Air inlet temperature
°C
20
°F
68
Exhaust back pressure
mbar(g)
0
psi
0
Ambient barometric pressure
mbar(a)
1013
psi
14.7
Limitations
Minimum ambient temperature
ºC
0
ºF
32
Maximum ambient temperature
ºC
46
ºF
115
Minimum allowable inlet temperature
ºC
10
ºF
14
Maximum allowable inlet temperature
ºC
70
ºF
158
Maximum (absolute) inlet pressure
mbar(a)
1050
psi
0.73
Maximum vessel pressure (mbar(g))
mbar(a)
1500
psi
7.3
9.4 Vacuum pump data
Reference condition
NOTICE!
All data specified below apply under reference conditions, see section Reference conditions and
limitations.
Summary of Contents for QSV 2200
Page 1: ...Quincy Oil sealed rotary screw vacuum pumps QSV 2200 QSV 2700 QSV 3200 Instruction Manual...
Page 2: ......
Page 4: ...This page intentionally left blank...
Page 14: ...Section II General description 14 Quincy Vacuum Pump QSV Series Open view front Open view back...
Page 61: ...Section IV Installation Quincy Vacuum Pump QSV Series 61 Installation 4 1 Dimension drawings...
Page 62: ...Section IV Installation 62 Quincy Vacuum Pump QSV Series 4 2 Installation proposal...
Page 122: ...Notes 122 Quincy Vacuum Pump QSV Series...
Page 123: ......
Page 124: ...www quincycompressor com No 6996 0227 39 2017 09 Printed in USA...