• I = 128 A + 25 % = 128 x 1.25 = 160 A
• For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
• Install the prescribed maximum fuse (150 A) on each cable
• Parallel supply cable (2 x 3 2 PE - configuration (2)):
• I = (128 A + 25%)/2 = (128 x 1.25)/2 = 80 A
• For a AWG4, the maximum current is 85 A x 0.8 = 68 A, which is insufficient. For an
AWG3, the maximum current is 100 x 0.8 = 80 A. So 2 parallel cables of 3 x AWG3 + 2
x AWG8 are sufficient.
• Install 80 A fuses on each cable.
8.3
Protection settings
Setting motor overload relay (F21)
Frequency (Hz)
Voltage (V)
40HP F21 (A) 50HP F21 (A) 60HP F21 (A)
UL/cUL
60
230
67.9
77.0
96.3
50
380
40.2
47.8
57.1
60
380
40.9
48.5
58.4
60
460
33.9
39.8
48.5
60
575
27.4
31.9
38.5
Settings for fan motor overload protection (Q15)
Frequency (Hz)
Voltage (V)
40HP Q15 (A) 50HP Q15 (A) 60HP Q15 (A)
UL/cUL
60
230
4.2
4.2
5.8
50
380
2.8
2.8
2.8
60
380
2.4
2.4
3.5
60
460
2.4
2.4
3.2
60
575
1.9
1.9
2.6
8.4
Dryer switches
General
The regulating and safety devices are factory-adjusted to give optimum performance of the dryer.
Do not alter the setting of any of the devices.
Instruction book
2920 7190 02
101
Summary of Contents for QGD 40
Page 1: ...Quincy Oil injected rotary screw compressors QGD 40 QGD 50 QGD 60 Instruction book...
Page 2: ......
Page 14: ...Front view compressors with integrated dryer Instruction book 12 2920 7190 02...
Page 15: ...Front view open compressors without dryer Instruction book 2920 7190 02 13...
Page 16: ...Rear view compressors without dryer Instruction book 14 2920 7190 02...
Page 17: ...Front view open compressors with integrated dryer Instruction book 2920 7190 02 15...
Page 112: ......
Page 113: ......