Installation, Operation and Maintenance Instructions
– Read and Save These Instructions –
This manual is provided to acquaint you with
the dehumidifier so that installation, operation
and maintenance can proceed successfully.
Ultimate satisfaction depends on the quality
of installation and a thorough understanding
of this equipment. The dehumidifier is built
around tested engineering principles and has
passed a thorough inspection for quality of
workmanship and function.
Quest DRY 150
Installation, Operation and Maintenance Instructions
4201 Lien Rd
Phone 608-237-8400
Madison, WI 53704
Toll-Free 1-800-533-7533
www.QuestProtect.com [email protected]
– Read and Save These Instructions –
Specifications subject to change without notice.
TS-397
04/12
1
Quest DRY 115
Quest DRY 115:
• Low dewpoint operation
• 115 Pints/Day @ AHAM
• Wide operating range
• 22 Amps total power consumption
• Factory installed 115VAC power cords
(2 required @ 15 Amps each)
• Simple ON/OFF operation with available
low voltage control kit for remote/
dehumidistat operation
• Vertical or horizontal operation
• Multiple ducting options
Water Removal Rates (Pints/Day)
56 Pints
100°F, 20%
160 Pints
90° F, 90%
135 Pints
80° F, 80%
115 Pints
80° F, 60% (AHAM)
115 Pints
70° F, 80%
105 Pints
70° F, 60%
105 Pints
60° F, 80%
100 Pints
60° F, 60%
110 Pints
50° F, 80%
90 Pints
50° F, 60%
25 Pints
10° F, 80%
quest
quest