QUEST 746

 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

QUESTCLIMATE.COM

(877) 420-1330

1.  INTENDED APPLICATION FOR QUEST 746

The Quest 746 Dehumidifier is designed to operate in temperatures between 56 F and 95 F. 
In order to efficiently control humidity levels, the area in which the dehumidifier is to be operated must 
be free of water intrusion or excessive fresh (outside) air infiltration. Before installing the Quest 746 
Dehumidifier, water intrusion and air infiltration problems should be addressed or noted in calculations.

2. REGISTRATIONS

The Quest 746 Dehumidifier units conform to unified standards: UL 60335-2-40, CSA 22.2 # 60335-2-
40:2012 Ed. 1+4. Patent:

 thermastor.com/patents

3. SPECIFICATIONS @ 80°F /60% RH

UNIT

QUEST 746 

 

4037610

CFM:

1750 @ 0.0” WG

POWER:

4300 Watts

SUPPLY VOLTAGE:

480 VAC  

3 Phase - 60 Hz

CURRENT DRAW:

6.5A

RATED CURRENT DRAW: 

(104 F 

36%)

7.5A

MCA 

*

10A

MOP *

15A

RECOMMENDED BREAKER SIZE:

10A

ENERGY FACTOR (L/KWH):

3.45

OPERATING TEMP:

56 F Min –

 

95 F Max

WATER REMOVAL (PINTS/DAY): 

EFFICIENCY (PINTS/KWH):

746 

7.3

AIR FILTER (MERV-13):  

(

QTY

 2)

Size: 18” x 20” x 2”

POWER CORD:

No cord; hardwire only

ELECTRICAL KNOCKOUT SIZE:

3/4” (1.094” opening)

DRAIN CONNECTION:

3/4” Threaded NPT

REFRIGERANT TYPE:

REFRIGERANT AMOUNT:

R410A 

6 lb 4 oz

DIMENSIONS: 

WIDTH: 

HEIGHT: 

LENGTH: 

WEIGHT:

Unit 

Shipping 

28.9” 

 36” 

34.1” 

 40” 

44.8” 

 48” 

340 lb 

 420 lb

* MCA = Minimum Circuit Ampacity  

This number provides a qualified electrician 
with the information needed to determine 
the minimum wire size used in the circuit that 
feeds a single dehumidifier.

* MOP = Maximum Overcurrent Protection 

This number provides a qualified electrician 
with the value of the maximum size circuit 
breaker that may be used to protect the 
circuit that feeds a dehumidifier.

This unit requires external control, not provided. 
Specifications are subject to change without notice.

Summary of Contents for 746

Page 1: ...astor com patents T S 2005 02 24 R E V D Quieter Operation Patented M CoRR Technology Industry Leading Efficiency Superior MERV 13 Air Filtration Integrated Lift and Hang Points Auto Restart After Pow...

Page 2: ...ons 6 5 1 Humidity Control 6 5 2 24VAC Wiring 6 5 2A Deh 3000R 7 5 2B Honeywell Remote Humidistat 7 5 2C Daisy Chain 7 Maintenance 8 6 1 Standard Air Filter 8 7 Service 8 7 1 Warranty 8 7 2 Technical...

Page 3: ...an outlet that is a GROUND FAULT INTERRUPT protected circuit DO NOT use the device as a bench or table DO NOT place the device directly on structural members Provide vibration isolation in order to m...

Page 4: ...se 60 Hz CURRENT DRAW 6 5A RATED CURRENT DRAW 104 F 36 7 5A MCA 10A MOP 15A RECOMMENDED BREAKER SIZE 10A ENERGY FACTOR L KWH 3 45 OPERATING TEMP 56 F Min 95 F Max WATER REMOVAL PINTS DAY EFFICIENCY PI...

Page 5: ...wired directly to the electrical service The current draw under normal operating conditions is listed in section 3 Information required for proper electrical service installation and overcurrent prote...

Page 6: ...mation on the kit FOLLOW DIAGRAM Level unit within 2 4 4 HANGING DIAGRAM WARNING Hanging installation must meet all state and local codes WARNING Installation should be done by a qualified agency in a...

Page 7: ...Control DEH 3000R Honeywell Humidistat Any 24V signal to dehumidify CAUTION Low Voltage Hazard Can cause equipment damage Disconnect power before beginning installation 5 2 24VAC WIRING The terminal b...

Page 8: ...MOTE HUMIDISTAT WIRING DIAGRAM QUEST DEH 3 WIRING Red Black C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT 24VAC COMP FAN QUEST DEH 3000R CONTROLER C FAN R DHU...

Page 9: ...property damage Only qualified service personnel should service this unit 7 1 WARRANTY A warranty certificate has been enclosed with this unit read it before any repair is initiated If a warranty repa...

Page 10: ...sure to use appropriate size duct branches to maintain proper feed throughout the ducting system System control should be placed remotely from the dehumidifier in a central location Intake and exhaust...

Page 11: ...a menu selection screen moves cursor up On an editable value increases the value Press and hold to change the value faster If cursor is in upper left corner of a screen moves to previous screen Enter...

Page 12: ...rom any screen press the Prg Bullseye key This will prompt for a password 2 Press Enter four times to access the menu Then press Up Down keys until Settings is highlighted 3 Press Enter to enter Setti...

Page 13: ...rm key If there are active alarms this will display a screen like this 2 Press Up Down to cycle through all active alarms The alarms are arranged in order of their alarm code lowest to highest One scr...

Page 14: ...een except for a few differences The Alarm Log screen does not display the current operating mode The Alarm Log screen shows both when the alarm was first triggered Event Start and when the fault cond...

Page 15: ...HANDLE POCKET QTY 4 14 4038136 BEZEL HANDLE QTY 4 Item Part No Description 15 4042586 WIRE HARNESS NOT SHOWN 16 4038079 LUG GROUND 17 4038219 FOOT RUBBER 1 25 DIA QTY 4 18 4038225 01 BRACKET FOOT RIGH...

Page 16: ...15 QUEST 746 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330...

Page 17: ...16 QUEST 746 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330 WIRING DIAGRAM OF THE QUEST 746 DEHUMIDIFIER 4042587 REV B...

Page 18: ...17 QUEST 746 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330 SEE BACK FOR WARRANTY AND REGISTRATION...

Page 19: ...sion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control LIMITATIONS AND EXCLUSIONS I...

Reviews: