background image

9

BREAK

OUT

Figure 4A

Figure 4B

Installation

Alarm Tamper-Resist  Feature

• A tamper resist feature has been provided. To activate

this feature you must break out the tamper-resist
blocks on the mounting plate (Figure 4A). Use a small
screwdriver.

• Using this feature will deter children and others from

removing the alarm from the mounting plate.

• The tamper-resist tab will have to be released in order

to change the battery. Using a tool (small screwdriver)
push the tab away from the mounting plate (Figure 4B)
and rotate the alarm anti-clockwise in the “OFF”
direction.

• After installation, test the alarm by depressing and

holding down the Test button for several seconds. This
should sound the alarm.

0946-7219-00(135997_135998)_V3C.qxd:_  2013

Summary of Contents for Q946

Page 1: ...fferent ways and are often unpredictable For maximum protection against fast flaming fires and slow smouldering fires both ionisation and photoelectric alarms should be installed Quell is a registered trademark of Chubb Fire Security Pty Ltd Copyright 2013 Chubb Fire Security Pty Ltd All rights reserved P N 135997 135998 0946 7219 00 0946 7219 00 135997_135998 _V3C qxd _ 2013 ...

Page 2: ...NING Removal of the smoke alarm battery will render the smoke alarm inoperative IMPORTANT Read all instructions before installation and keep this manual near the alarm for future reference 1 This smoke alarm uses an extremely small amount of radioactive element in the ionisation chamber see warning on page 18 Do not try to repair the smoke alarm yourself Refer to the instructions in the warranty s...

Page 3: ... Figure 1C Things to Consider For Ceiling Mounting Smoke from a fire will rise to the ceiling and spread horizontally Mounting the smoke alarm in the centre of the ceiling places it closest to all points in the room When mounting an alarm on the ceiling locate it at a minimum of 30cm from the side wall Figure 2A For sloped peaked or cathedral ceilings the alarm should be placed between 500mm and 1...

Page 4: ...ms for Additional Protection KITCHEN BEDROOM BEDROOM BEDROOM LIVING ROOM KITCHEN BEDROOM BEDROOM HALL BASEMENT Figure 1A Figure 1C Figure 1B SINGLE FLOOR PLAN MULTIPLE FLOOR PLAN BEDROOM FAMILY ROOM WORKSHOP BASEMENT KITCHEN HALL GARAGE MASTER BEDROOM FIRE EXTINGUISHERS SMOKE ALARMS FIRE BLANKET TOTAL HOME PROTECTION 0946 7219 00 135997_135998 _V3C qxd _ 2013 ...

Page 5: ...BLE PLACEMENT DO NOT INSTALL DEAD AIR NOT IN THIS AREA ANYWHERE IN THIS AREA NOT IN THIS AREA ANYWHERE IN THIS AREA PEAK CEILING SLOPED CEILING 500mm 1000mm 1000mm 500mm Smoke alarm should be located between 500mm and 1500mm of the highest point DEAD AIR DEAD AIR DO NOT INSTALL DO NOT INSTALL 0946 7219 00 135997_135998 _V3C qxd _ 2013 ...

Page 6: ...the smoke from reaching an alarm mounted on the ceiling For Poorly Insulated Mobile Homes Install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 10cm and a maximum of 30cm below the ceiling Figure 2A For minimum protection install at least one alarm close to the bedrooms For additional protection see Figure 1A WARNING TEST YOUR SMOKE ALARM OPERATION AFTER CARAVAN ...

Page 7: ...sty dirty or greasy areas Do not install in areas where the temperature is colder than 5 C or hotter than 45 C Do not install in areas where the relative humidity RH is greater than 85 Avoid placing smoke alarms in kitchen areas If a kitchen alarm is desired it should have an alarm silencer feature or be a photoelectric type Do not place in the garage Avoid dead air spaces such as the peak of an A...

Page 8: ...e through the pencil marks and use the enclosed screws and anchors to secure the mounting plate Use a 3 16 inch drill bit to screw the anchor holes Press the battery reminder tab down into the battery compartment while inserting the battery Figure 3E WARNING Please ensure batteries are inserted correctly with positive and negative terminals connected to the corresponding point on the smoke alarm C...

Page 9: ...igure 3A Figure 3C Figure 3D A LINE ALIGNMENT MARKS WALL MOUNTING POSITION ROTATE TO MOUNT OR TO REMOVE Figure 3B _ _ Figure 3E BATTERY REMINDER TAB Installation 0946 7219 00 135997_135998 _V3C qxd _ 2013 ...

Page 10: ... deter children and others from removing the alarm from the mounting plate The tamper resist tab will have to be released in order to change the battery Using a tool small screwdriver push the tab away from the mounting plate Figure 4B and rotate the alarm anti clockwise in the OFF direction After installation test the alarm by depressing and holding down the Test button for several seconds This s...

Page 11: ... sound coming from your alarm may indicate a defective alarm see Warranty section NOTE WEEKLY TESTING IS REQUIRED LED Indicators This alarm is equipped with a red LED indicator with three modes of operation Red LED Flashing every 40 50 seconds Indicates that the smoke alarm is operating properly Red LED Flashing When the Test button is pressed or when the smoke alarm senses particles of combustion...

Page 12: ...mporarily desensitised condition The smoke alarm will automatically reset after approximately 8 minutes If after this period particles of combustion are still present the alarm will sound again The alarm silencer HushTM can be used repeatedly until the air has been cleared of the condition causing the alarm NOTE Dense smoke will override the alarm silencer HushTM and sound a continuous alarm CAUTI...

Page 13: ...4A Panasonic 6AM6 6AM 6 6AM 6PI 6AM6X or 6LR61 GA Lithium Type Ultralife U9VL J These batteries can be purchased at your local retailer WARNING Use only the batteries specified above To the extent permitted by law Chubb Fire Security Pty Ltd excludes all liability for loss or damage to the extent caused by the use of batteries other than Eveready 1222 Gold peak 1604S Energizer 522 Duracell MN1604 ...

Page 14: ... entering the unit After cleaning reinstall your alarm and test your alarm by using the Test button If cleaning does not restore the alarm to normal operation the alarm should be replaced Do not paint the unit Paint will seal the vents and interfere with the sensor s ability to detect smoke Never attempt to disassemble the unit or clean inside This action will void your warranty Replacing the Alar...

Page 15: ...the AC power has been cut off such as by an electrical fire or an open fuse Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are in good operating condition Smoke alarms cannot provide an alarm if smoke does not reach the alarm Therefore smoke alarms may not sense fires starting in chimneys walls on roofs on the other side of a closed door or on a different f...

Page 16: ... permitted Smoke Detection Are more smoke alarms desirable The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms For this reason it is recommended that the householder consider the use of additional smoke alarms for those areas for increased protection The additional areas in...

Page 17: ...ond counts so don t waste time getting dressed or picking up valuables In leaving don t open any inside door without first feeling its surface If hot or you see smoke seeping through cracks don t open that door Instead use your alternative exit If the inside of the door is cool place your shoulder against it open it slightly and be ready to slam it shut if heat and smoke rush in Stay close to the ...

Page 18: ...offered for sale in New Zealand the benefits to the consumer given by this warranty are in addition to other rights and remedies of the consumer under relevant New Zealand consumer protection laws and other applicable laws relating to the goods Our goods come with guarantees that cannot be excluded under relevant New Zealand consumer protection laws You are entitled to a replacement or refund for ...

Page 19: ...ect in the product appears within the time frame stated you are entitled to submit a warranty claim by returning your product to the address shown below Please contact Chubb on the telephone numbers provided below Monday to Friday during 9 00AM 5 00PM When returning the product please ensure it is properly packaged so that no damage occurs during transit Any postage and packaging expenses required...

Reviews: