Parameter no. 40 – Power reporting in
Watts on power change
Set value means percentage, set value from 0
- 100=0% - 100%. Available configuration
parameters (data type is 1 Byte DEC):
•
default value 3
•
0 – Reporting Disabled
•
1 – 100 = 1% - 100% Reporting enabled
Power report is send (push) only when
actual power in Watts in real time changes
for more than set percentage comparing
to previous actual power in Watts, step is
1%.
NOTE:
if power changed is less than 1W, the
report is not send (pushed), independent of
percentage set.
Parameter no. 42 – Power reporting in
Watts by time interval
Set value means time interval (0 – 65535) in
seconds, when power report is send.
Available configuration parameters (data type
is 2 Byte DEC):
•
default value 300 (power report in Watts is
send each 300s)
•
0 – Reporting Disabled
•
1 – 65535 = 1second – 65535 seconds.
Reporting enabled. Power report is send
with time interval set by entered value.
Technical Specifications
Power supply
110 - 230 VAC ±10%
50/60Hz, 24-30VDC
Rated load current of AC
output (resistive load)*
1 X 10A / 230VAC
Rated load current of DC
output (resistive load)
1 X 10A / 30VDC
Output circuit power of
AC output (resistive
load)
2300W (230VAC)
Output circuit power of
DC output (resistive
load)
240W (24VDC)
Power measurement
accuracy
P=5-50W, +/-3W
P>50W, +/-3%
Digital temperature
sensor range (sensor
must be ordered
separately)
-50 ~ +125°C
Operation temperature -10 ~ +40°C
Distance
up to 30 m indoors
(depending on
building materials)
Dimensions (W x H x D) 41,8 x 36,8 x 15,4mm
Weight
25g
Electricity consumption 0,4W
For installation in boxes Ø
≥
60mm or 2M
Switching
Relay
* In case of load other than resistive, pay
attention to the value of cos
φ
and if necessary
apply load lower than the rated load. Max
current for cos
φ
=0,4 is 3A at 250VAC, 3A at
24VDC L/R=7ms.
Z-Wave Device Class:
BASIC_TYPE_ROUTING_SLAVE
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Z-Wave Supported Command Classes:
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY
COMMAND_CLASS_SWITCH_ALL
COMMAND_CLASS_METER_V3
COMMAND_CLASS_SENSOR_MULTILEVEL_V3
COMMAND_CLASS_MULTI_CHANNEL_V2
COMMAND_CLASS_POWERLEVEL
COMMAND_CLASS_ASSOCIATION
COMMAND_CLASS_CONFIGURATION
COMMAND_CLASS_MANUFACTURER_SPECIFIC
COMMAND_CLASS_VERSION
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
Endpoint 1 (I2):
Device Class:
GENERIC_TYPE_SENSOR_BINARY
SPECIFIC_TYPE_NOT_USED
Command Classes:
COMMAND_CLASS_SENSOR_BINARY
COMMAND_CLASS_BASIC
Endpoint 2 (I3):
Device Class:
GENERIC_TYPE_SENSOR_BINARY
SPECIFIC_TYPE_NOT_USED
Command Classes:
COMMAND_CLASS_SENSOR_BINARY
COMMAND_CLASS_BASIC
This product can be included and operated in
any Z-Wave network with other Z-Wave
certified devices from any other manufacturers.
All constantly powered nodes in the same
network will act as repeaters regardless of the
vendor in order to increase reliability of the
network.
Important disclaimer
Z-Wave wireless communication is inherently
not always 100% reliable, and as such, this
product should not be used in situations in
which life and/or valuables are solely
dependent on its function.
Warning!
Do not dispose of electrical appliances as
unsorted municipal waste, use separate
collection facilities.
Contact your local government for information
regarding the collection systems available. If
electrical appliances are disposed of in landfills
or dumps, hazardous substances can leak into
the groundwater and get into the food chain,
damaging your health and well-being. When
replacing old appliances with new once, the
retailer is legally obligated to take back your
old appliance for disposal at least for free of
charge.
This user manual is subject to change and
improvement without notice.
Qubino
Goap d.o.o. Nova Gorica
Ulica Klementa Juga 007
5250 Solkan
Slovenia
E-mail:
Tel: +386 5 335 95 00
Web:
www.qubino.com
Date: 8.12.2014
Document: Qubino_Flush 1
relay user
manual_V6.3_eng
Parameter no. 40 – Power reporting in
Watts on power change
Set value means percentage, set value from 0
- 100=0% - 100%. Available configuration
parameters (data type is 1 Byte DEC):
•
default value 3
•
0 – Reporting Disabled
•
1 – 100 = 1% - 100% Reporting enabled
Power report is send (push) only when
actual power in Watts in real time changes
for more than set percentage comparing
to previous actual power in Watts, step is
1%.
NOTE:
if power changed is less than 1W, the
report is not send (pushed), independent of
percentage set.
Parameter no. 42 – Power reporting in
Watts by time interval
Set value means time interval (0 – 65535) in
seconds, when power report is send.
Available configuration parameters (data type
is 2 Byte DEC):
•
default value 300 (power report in Watts is
send each 300s)
•
0 – Reporting Disabled
•
1 – 65535 = 1second – 65535 seconds.
Reporting enabled. Power report is send
with time interval set by entered value.
Technical Specifications
Power supply
110 - 230 VAC ±10%
50/60Hz, 24-30VDC
Rated load current of AC
output (resistive load)*
1 X 10A / 230VAC
Rated load current of DC
output (resistive load)
1 X 10A / 30VDC
Output circuit power of
AC output (resistive
load)
2300W (230VAC)
Output circuit power of
DC output (resistive
load)
240W (24VDC)
Power measurement
accuracy
P=5-50W, +/-3W
P>50W, +/-3%
Digital temperature
sensor range (sensor
must be ordered
separately)
-50 ~ +125°C
Operation temperature -10 ~ +40°C
Distance
up to 30 m indoors
(depending on
building materials)
Dimensions (W x H x D) 41,8 x 36,8 x 15,4mm
Weight
25g
Electricity consumption 0,4W
For installation in boxes Ø
≥
60mm or 2M
Switching
Relay
* In case of load other than resistive, pay
attention to the value of cos
φ
and if necessary
apply load lower than the rated load. Max
current for cos
φ
=0,4 is 3A at 250VAC, 3A at
24VDC L/R=7ms.
Z-Wave Device Class:
BASIC_TYPE_ROUTING_SLAVE
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Z-Wave Supported Command Classes:
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY
COMMAND_CLASS_SWITCH_ALL
COMMAND_CLASS_METER_V3
COMMAND_CLASS_SENSOR_MULTILEVEL_V3
COMMAND_CLASS_MULTI_CHANNEL_V2
COMMAND_CLASS_POWERLEVEL
COMMAND_CLASS_ASSOCIATION
COMMAND_CLASS_CONFIGURATION
COMMAND_CLASS_MANUFACTURER_SPECIFIC
COMMAND_CLASS_VERSION
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
Endpoint 1 (I2):
Device Class:
GENERIC_TYPE_SENSOR_BINARY
SPECIFIC_TYPE_NOT_USED
Command Classes:
COMMAND_CLASS_SENSOR_BINARY
COMMAND_CLASS_BASIC
Endpoint 2 (I3):
Device Class:
GENERIC_TYPE_SENSOR_BINARY
SPECIFIC_TYPE_NOT_USED
Command Classes:
COMMAND_CLASS_SENSOR_BINARY
COMMAND_CLASS_BASIC
This product can be included and operated in
any Z-Wave network with other Z-Wave
certified devices from any other manufacturers.
All constantly powered nodes in the same
network will act as repeaters regardless of the
vendor in order to increase reliability of the
network.
Important disclaimer
Z-Wave wireless communication is inherently
not always 100% reliable, and as such, this
product should not be used in situations in
which life and/or valuables are solely
dependent on its function.
Warning!
Do not dispose of electrical appliances as
unsorted municipal waste, use separate
collection facilities.
Contact your local government for information
regarding the collection systems available. If
electrical appliances are disposed of in landfills
or dumps, hazardous substances can leak into
the groundwater and get into the food chain,
damaging your health and well-being. When
replacing old appliances with new once, the
retailer is legally obligated to take back your
old appliance for disposal at least for free of
charge.