B.E.S. - BOWLER ENTERTAINMENT SYSTEM
Pre-Installation Manual
Copyright 2007 Qubica S.p.A.
March 2007 – rev. 2B
6
US Only - Three wire circuit with continuous insulated third wire (Green) equipment ground
connecting to the service entrance positive earth ground for each group of four lanes is required.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
A twist lock plug or 3 prong ground male plug must be provided to attach to the monitor power
cord in order the match the twist lock or grounded receptacle located above the overhead
housing. Each pair of monitors requires 7.5 Amps of power.
Maximum power consumption of a single Overhead Monitor is 100 Watts.
A.1.5
Front Desk Computer
Provisions are required at the control desk to locate the front desk computer, monitor, UPS and
any peripherals being installed for this terminal. (Qubica will provide (1) UPS per front desk
station - only U.S. market)
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit is required for the front desk.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
U.S. only - A three wire dedicated 120V 20A - 240V 10A p 50/60 Hz circuit with an isolated
ground outlet is required. This outlet must have a continuous, insulated, third wire (green)
equipment ground connecting to the service entrance positive earth ground only. This circuit
shall not be connected to or used by any other equipment other than the equipment described
above. Each front desk system requires 6 Amps of power.
Maximum power consumption of Front Desk PC plus Monitor is 500 Watts.
A single power line must be set up for each Front Desk or Back Office Computer.
A.1.6
Back Office Computer
Provisions are required in the back office to locate the back office computer, monitor, UPS and
any peripherals being installed for this terminal. (Qubica will provide (1) UPS per back office
station - only U.S. market)
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit is required for the back office.
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
U.S. only - A three wire dedicated 120V 20A - 240V 10A p 50/60 Hz circuit with an isolated
ground outlet is required. This outlet must have a continuous, insulated, third wire (green)
equipment ground connecting to the service entrance positive earth ground only. This circuit
shall not be connected to or used by any other equipment other than the equipment described
above. Each back office system requires 6 Amps of power.
Maximum power consumption of Back Office PC plus Monitor is 500 Watts.
A single power line must be set up for each Front Desk or Back Office Computer.
A.1.7 XS
Bumpers
A dedicated 120V 20A - 240V 10A 50/60 Hz circuit is required for each group of 24 lanes (12
pairs).
Use no wire smaller than number 12 AWG - 2 mm Ø , rated at 600 Volts.
U.S. only - A three-wire 120V 20A - 240V 10A 50/60 Hz circuit with a continuous, insulated,
third wire (green) equipment ground connecting to the service entrance positive earth ground for
each group of 24 lanes (12 pairs) is required. A grounded duplex outlet receptacle, such as
Hubbell type, located at on the pinsetter side of the curtain wall, centered on a 24-lane section,
is required. The transformer supplied by Qubica will utilize this receptacle.