7 48008002-06
Pre Unit Installation:
1. Ensure when positioning the units that suitable access is available for removing air filter and other routine maintenance
including the removal of coils and fans.
2. Identify the correct units
3. Before removing any packaging check the identity of the fan coil against identity labels on the unit.
Fitting Units
1. Prepare drop rods ready to accept the fan coil units M6,M8 or M10
2. Fit washers and nuts onto drop rods before lifting the unit
3. Use the lock nuts to level the unit and then lock in position
[Note: Studding, nuts and washers not supplied with units]
Fig 3.
4. Packaging should be left in place to protect the unit until ready for fitting.
5.
DO NOT USE THE DRAIN TRAY OR PIPES/ VALVES TO LIFT THE UNIT INTO POSITION
6. Suspended the fan coil on the drop rods, level the unit up using a spirit level checking to ensure the unit sits level in both
directions.[the drip tray is designed with a built in fall to ensure condensation runs to the drain connection]
7. Use nuts and washers to secure unit in position.
Units supplied with condensation pumps fitted. [Factory fit option]
8. The float switch is packed in a plastic bag and stored in the drain tray to avoid it being damaged during transit. The float
switch will require fitting to the drain tray drain stub and securing in position using the nylon cable tie supplied.
9. Once the fan coil is fitted it is
important
to ensure that the float valve sits level and the vent pipe terminates higher than
the condensation tray see fig 5
Fitting the Float Switch on site on units with factory fitted. condensation pump
10. The float switch / mounting bracket assembly must be assembled to the drain pipe on site during installation.
The Float switch is supplied pre piped and packed in the drain tray. See Fig. 4
Fig. 4
Float Switch & Cable Tie Packed