Pre Unit Installation: 

1.  Ensure when positioning the units that suitable access is available for removing air filter and other routine maintenance 

including the removal of coils and fans. 

2.  Identify the correct units 
3.  Before removing any packaging check the identity of the fan coil against identity labels on the unit. 

 
 
Fitting Units 

1.  Prepare drop rods ready to accept the fan coil units M6,M8 or M10         
2.  Fit washers and nuts onto drop rods before lifting the unit 
3.  Use the lock nuts to level the unit and then lock in position 

 

[Note: Studding, nuts and washers not supplied with units] 

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Fig 3. 

 
 
 

4.  Packaging should be left in place to protect the unit until ready for fitting. 
5. 

DO NOT USE THE DRAIN TRAY OR PIPES/ VALVES TO LIFT THE UNIT INTO POSITION

                                                                                             

 

6.  Suspended the fan coil on the drop rods, level the unit up using a spirit level checking to ensure the unit sits level in both 

directions.[the drip tray is designed with a built in fall to ensure condensation runs to the drain connection]  

7.  Use nuts and washers to secure unit in position.                                                                                                

 

Units supplied with condensation pumps fitted. [Factory fit option] 

8.  The float switch is packed in a plastic bag and stored in the drain tray to avoid it being damaged during transit. The float 

switch will require fitting to the drain tray drain stub and securing in position using the nylon cable tie supplied. 

9.  Once the fan coil is fitted it is 

important

 to ensure that the float valve sits level and the vent pipe terminates higher than 

the condensation tray see fig 5 

 

 
Fitting the Float Switch on site on units with factory fitted. condensation pump  

 

10.  The float switch / mounting bracket assembly must be assembled to the drain pipe on site during installation. 

 

The Float switch is supplied pre piped and packed in the drain tray. See Fig. 4 

 
 
 
 
 
 
      
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Fig. 4 

 
 

Float Switch & Cable Tie Packed  

Summary of Contents for AMB 1

Page 1: ...Units Designed for Ceiling or Void Mounting INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS TEV Ltd Armytage Road Brighouse West Yorkshire United Kingdom HD6 1QF UK Tel 01484 405630 Fax 01484 405620...

Page 2: ...e used 4 It is manually isolated from the electrical mains supply 5 Electrical equipment is earthed to comply with IEE regulations and local by laws 6 All electrical work must be carried out by a Qual...

Page 3: ...ntation 5 Filters 5 INSTALLATION Dimensional details 6 Pre Unit Installation 7 Fitting unit 7 Fitting float switch 7 9 Connection of ductwork 9 COMMISIONING Airside Measuring and Balancing 10 Electric...

Page 4: ...s AC Speed control of the fan motors is achieved by means of a multitapped auto transformer which is wired to a three speed and fine adjustment switches Supplied with continuous filament media filters...

Page 5: ...aged Maintenance It is essential that the following instructions as laid down in this section are carried out and maintained during the period of storage before commissioning Internal Surfaces If duct...

Page 6: ...B Spigot Options Weight approx Kg AMB 1 630 595 1 2 3 4 37 AMB 2 880 845 1 2 3 4 45 AMB 3 1230 1195 1 2 3 4 5 55 AMB 4 1230 1195 1 2 3 4 5 60 AMB 5 1430 1395 1 2 3 4 5 70 AMB 6 1430 1395 1 2 3 4 5 75...

Page 7: ...unit up using a spirit level checking to ensure the unit sits level in both directions the drip tray is designed with a built in fall to ensure condensation runs to the drain connection 7 Use nuts and...

Page 8: ...nt pipe is higher than the water level in the drip tray 13 The drain pipe from the condensate pump must be run to a common drain It is important that any condensate pump installed must be in accordanc...

Page 9: ...Typical installation showing ductwork connected to unit The ducts should be pushed fully over the spigot up to the outer casing of the unit and secured to the spigot with screws once fitted they shou...

Page 10: ...ation of the condensation pump by pouring a small amount of water into the drain tray and ensure the pump clears any water and operates any alarms etc 13 Start the fan and blow through the system thor...

Page 11: ...ice and maintenance of Quartz fan coil units and must be read before any maintenance is attempted WARNING It is essential that before any work is carried out the unit is isolated externally from the e...

Page 12: ...ws and slide element upwards letting the screw head pass through the key hole slots 5 Remove wires from element take note of terminal connections used 6 Remove elements from the unit must be replaced...

Page 13: ...irty filters will reduce the air volume handled by the unit thus adversely affecting its performance The length of time between cleaning of filters is dependant upon the environment A six to twelve mo...

Page 14: ...emperatures Alternatively Electric Heating elements are available and can be supplied wired for single phase or three phase supply as appropriate or as specified Multiple units fitted on the same syst...

Reviews: