Module Remove and Replace 207
3
Slide the fan into the slot until the latch clicks home.
The chassis should automatically detect and make use of the new module.
4
Wait for the Module OK LED on the newly inserted fan to illuminate green. See also
page 205.
• If the Module OK LED does not illuminate, verify that the fan is properly inserted and seated in
the slot.
• If properly seated, the module may be defective. Check the disk management utility (GUI) and
the event logs for more information.
• Using the management interfaces (the disk management utility (GUI) or CLI), determine if the
health of the new fan is OK. Verify that the Module OK LED is green, and that the Ops panel
states show no amber module faults.
5
If replacing multiple fans, repeat
.
Replacing a 5U84 RAID Controller or Expansion IOM
The QXS-G2-412, QXS-G2-424, and QXS-G2-484 systems support a common set of RAID controllers in
the RAID chassis, and a common expansion IOM in the expansion chassis, within supported 2U and
5U chassis configurations.
•
provides an illustration of the
CNC (FC/iSCSI Controller).
•
provides an illustration of the
Expansion IOM.
Figure 171
CNC (FC/iSCSI Controller)
Figure 172
Expansion IOM
С
Summary of Contents for QXS G2 Series
Page 1: ...QXS G2 Hardware Installation and Maintenance Guide 12 24 and 84 Drive Systems 6 68649 01 Rev A...
Page 126: ...114 QXS G2 Hardware Installation and Maintenance Guide...
Page 176: ...164 QXS G2 Hardware Installation and Maintenance Guide...
Page 232: ...220 QXS G2 Hardware Installation and Maintenance Guide...
Page 236: ...224 QXS G2 Hardware Installation and Maintenance Guide...
Page 246: ...234 QXS G2 Hardware Installation and Maintenance Guide...