background image

 

4. General requirements   

 

4.1.

The 

Quantum “Hot Spring

” domestic hot water cylinder 

MUST

 be installed by a  

competent person in accordance with section 

G3

 of the current 

Building Regulations

 

4.2. Important - 

It is important that the installer reads and understands these instructions, 

unpacks and familiarises themselves with the equipment before commencing the installation. 
Failure to observe these installation instructions could invalidate the warranty. 
 

4.3. Water supply

 - The warranty requires that the water to be heated be of drinking water 

quality and that if water treatment equipment is installed, it must function correctly. 
The unit, where possible should be fed via a 22 mm diameter supply pipe. It requires a supply 
pressure of 1.5 bar with a flow rate of at least 20 litres per minute as a minimum for it to 
function. Even with these rates, flow from the outlets will be disappointing if several outlets are 
used simultaneously. Generally speaking, the higher the supply pressure, the better the system 
will function. The cylinder control equipment is factory set to limit the system operating pressure 
to 3 bar. The maximum supply pressure into the pressure-reducing valve is 12 bar. 
 

4.4. Taps and fittings 

-

 

All taps and fittings incorporated in the unvented system should have a 

rated operating pressure of 7 bar or above. 
 

4.5. Location – 

The unit is designed to be floor standing, vertically mounted, indoors, in a frost-

free environment. When choosing a suitable location for the cylinder, consideration should be 
given to the routing of the discharge pipe to a convenient point and also the availability of an 
adequate power supply for connecting the immersion heater(s). 
The cylinder may stand on any flat and level surface without any special foundation 
preparations, provided that it is sufficiently robust to support the full weight of the cylinder. (See 
Technical specifications for weights) 
The position of the cylinder should be such that easy access is provided for servicing the controls 
and replacing the immersion heater should the need arise. 
Generally, pipe runs should be made as short as possible and lagged to prevent heat loss.  
  

4.6. Storage and handling – 

If the cylinder is not being installed immediately, it should remain 

in its carton with all pipe end protective caps in situ to to prevent damage. We recommend that 
the cylinder be transported to its installation position on a sack truck or similar with the outer 
carton in place. 
 

4.7. Pipework connections 

 

All Pipework connections to the cylinder 

MUST

 be made in 

accordance with Fig 1. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Hot Spring

Page 1: ...Storage Capacities 90 125 150 170 200 250 and 300 Litres Hot Spring Installation User and Service Manual Domestic Hot Water Cylinder...

Page 2: ...12 User instructions 20 13 Warranty 20 1 Introduction The Quantum Hot Spring is a high quality stainless steel domestic hot water cylinder suitable for use on unvented or open vented hot water systems...

Page 3: ...3 Performance Hot water generation time in minutes from 26 36 37 36 33 35 40 15 to 65 degrees C for Indirect cylinder Hot water generation time in minutes from 52 72 86 98 108 144 202 15 to 65 degrees...

Page 4: ...e is 12 bar 4 4 Taps and fittings All taps and fittings incorporated in the unvented system should have a rated operating pressure of 7 bar or above 4 5 Location The unit is designed to be floor stand...

Page 5: ...5 Pipework connections Fig 1 KEY ITEM DESCRIPTION A TEMPERAURE AND PRESSURE RELIEF VALVE B HOT WATER C HEATING WATER RETURN D THERMOSTAT POCKET E COLD WATER F IMMERSION HEATER G HEATING WATER FLOW...

Page 6: ...er demand before switching over on to central heating duty If an existing system is a flow share arrangement such as a Honeywell S or Y plan type system see Figs 3 and 4 they will also provide satisfa...

Page 7: ...7 W Plan wiring layout and system schematic...

Page 8: ...8 Fig 2 Y Plan wiring layout and system schematic...

Page 9: ...9 Fig 3 S Plan wiring layout and system schematic Fig 4...

Page 10: ...torage volumes up to and including 200 litres For cylinders of 250 and 300 litres capacity a separate 24 litre expansion vessel is supplied which MUST be connected into the cold water supply side betw...

Page 11: ...VALVE SET 6 BAR 6 DISCHARGE PIPE 22mm DIA SEE SECTION 7 7 DRAIN COCK 8 IMMERSION HEATER 230v 3 Kw 50 Hz 9 COLD WATER INLET CONNECTION 22mm DIA 10 PRIMARY FLOW CONNECTION 22mm DIA 11 CONTROL THERMOSTAT...

Page 12: ...Downward discharge at low level i e up to 100 mm above external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children play or otherwise come into co...

Page 13: ...13 Typical discharge pipe arrangement Fig 6...

Page 14: ...Worked example The example below is for a diameter temperature relief valve with a discharge pipe D2 having 4 No elbows and a length of 7 m from the tundish to the point of discharge From Maximum res...

Page 15: ...mit trip is factory set at 85 C The immersion heater conforms with EEC Directive 76 889 for radio interference and complies with BS 800 1977 WARNING Never fit an immersion heater without a thermal cut...

Page 16: ...ontact separation of at least 3 mm using 1 5mm sq flexible cable 85 deg C rubber insulated HOFR sheathed to comply with BS 6141 table 8 and must be fully earthed d The BEAB approval certification on t...

Page 17: ...the valve seating and to prove the correct function of the discharge arrangement 9 4 Check all joints for leaks rectify as necessary 9 5 Check that the control and high limit settings for the indirect...

Page 18: ...e PRV Check the strainer and if necessary remove any debris from in front of it Replace the cartridge 10 8 Check the charge pressure in the expansion vessel and top up as necessary The charge pressure...

Page 19: ...ult your boiler manufacturers instructions 3 High limit thermostat has 3 Check and re set tripped 4 Motorised valve malfunction 4 Check wiring and or plumbing connections to motorised valve Intermitte...

Page 20: ...ols supplied with the cylinder for a period of 2 years from the date of purchase provided that they have been installed for their intended use by a competent person and have not been modified in any w...

Reviews: