Chapter 3: DXi6902 FRU Removal and Replacement Procedures
Replacing the Node Hard Drive Backplane
Quantum DXi6902 User’s Guide
141
Figure 86 DXi6902 Node Hard
Drive Backplane
Replacing the Hard
Drive Backplane
This section describes how to remove and replace the hard drive
backplane in the DXi6902 Node. The hard drive backplane connects the
SAS hard drives in the Node to the PERC H710 integrated storage
controller.
Caution:
Use appropriate ESD precautions, including the use of a
grounding strap, when performing this procedure.
Removing and replacing the hard drive backplane in the Node includes
the following steps:
•
Removing a Failed Hard Drive Backplane
•
Installing a Replacement Hard Drive Backplane
Removing a Failed Hard Drive Backplane
To remove the hard drive backplane from the DXi6902 Node:
1
Shut down the system (see
Turning On and Shutting Down the
2
3
Remove the cooling fan assembly (see
Illustration
Description
Replacement hard drive
backplane
PN 8JR0H