Chapter 3: FRU Removal and Replacement Procedures
Replacing an Array Module Controller
Quantum DXi6900-S Field Service Manual
161
Figure 116:
Removing and Installing an Array Module Controller
4. Insert the controller air blocker into the open controller slot to make sure that correct airflow is
maintained.
Installing a Replacement Array Module Controller
To install the replacement Array module controller:
1. Remove the BBU from the failed Array module controller and install the BBU in the replacement
Replacing an Array Module BBU on the next page
).
2. Remove the controller air blocker from the controller slot.
3. Slide the replacement Array module controller into the empty bay until the controller snaps into place,
and push the handles into the closed position (see
).
4. Connect the SAS cables to the new controller (see
DXi6900-S Cabling Diagrams on page 190
):
5. Run
Factory Detect Hardware
from the
Service Menu
to detect the new hardware (see
).
6. In the remote management console, delete any administrative alerts and close any service tickets.
Note:
In certain conditions SANtricity may be needed to correct the Tray numbering scheme or to run
the Recovery GURU, please refer to .