SECTION 6 - OPERATION
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
6
PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0%
HPC SHUTDOWN POSITION = XX.X
With service level password access, navigate to the
following setup parameters and set them properly to
maintain approximately 1 in. coverage above the top of
the condenser subcooler in accordance with the refrig-
erant charge level description in
in this manual.
Default Values
A listing of the low and high limits, and default pro-
grammable values is noted in each display and can be
found in
. The English units are
exact values while the metric units are approximate.
Unit "SETUP MODE" will allow the programming all
of the programmable values that the user should never
change. These will either be programmed at the factory
or by service personnel on the job. This mode may be
entered by pressing the PROGRAM key, entering the
password "4245", and pressing
(ENTER) key.
PROGRAM HPC DIRECTION
◄► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0%
HPC MINIMUM POSITION = XX.X
TABLE 37 -
PROGRAM LIMITS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Chilled Liquid Leaving Temperature Cutout
Water
Cooling
—
—
36.0°F
—
—
2.2°C
Glycol
Cooling
5.0°F
36.0°F
36.0°F
15.0°C
2.2°C
2.2°C
Motor Current Limit
—
30% FLA
100% FLA
100% FLA
Pulldown Motor Current Limit
—
30% FLA
100% FLA
100% FLA
Pulldown Motor Current Limit Time
—
0 min
255 min
0 min
Motor Temperature Unload
—
150.0°F
250.0°F
240.0°F
65.6°C
121.1°C
115.6°C
Sys 1 Condenser Level Control Setpoint
—
20.0%
80.0%
33.0%
Sys 2 Condenser Level Control Setpoint
(Not displayed on tandem circuit units)
—
20.0%
80.0%
33.0%
Unit ID Number
—
0
7
0
Head Pressure Control
—
DISABLED
ENABLED
DISABLED
Head Pressure Setpoint
HPC Enabled
25.0 psid
(1.72 bard)
35.0 psid
(2.41 bard)
28 psid
(1.93 bard)
HPC Kp
HPC Enabled
0.1
50.0
5.0
HPC Ti
HPC Enabled
10 s
1000 s
50 s
HPC Td
HPC Enabled
0 s
60 s
0 s
HPC Direction
HPC Enabled
DIRECT
REVERSE
DIRECT
HPC Minimum Position
HPC Enabled
0.0%
100.0%
0.0%
HPC Shutdown Position
HPC Enabled
0.0%
100.0%
0.0%
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...