QUANTECH
64
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE 7 -
OPTIONAL ONE-PASS EVAPORATOR
ALL DIMENSIONS - INCHES (MM)
QTC4
A,B
C
D
E
NOZZLE
SIZE
WATER
VOLUME.
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MODEL
COND.
150
S
20.8
(528)
6.8
(173)
34.5
(876)
8
58
(220)
500
(32)
1970
(124)
165
H
20.8
(528)
29.2
(742)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
175
P
20.8
(528)
34.9
(886)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
185
S
19.8
(503)
17.7
(450)
56.8
(1443)
6
48
(182)
400
(25)
1230
(77)
185
H
19.8
(503)
61.5
(1562)
56.7
(1425)
6
48
(182)
400
(25)
1230
(77)
185
P
21
(533)
117.3
(2979)
56.1
(1425)
8
56
(220)
500
(32)
1970
(124)
175
C
20.8
(528)
1.7
(43)
38.1
(968)
8
71
(269)
590
(37)
2190
(138)
210
S
19.8
(503)
61.7
(1567)
56.8
(1443)
6
48
(182)
400
(25)
1230
(77)
210
H
20.8
(528)
34.9
(886)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
210
P
21
(533)
78.9
(2044)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
NOTE
: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
Summary of Contents for QTC4 STYLE A Series
Page 22: ...QUANTECH 22 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...QUANTECH 34 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...QUANTECH 56 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 90: ...QUANTECH 90 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 148: ...QUANTECH 148 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 160: ...QUANTECH 160 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 163: ...QUANTECH 163 FORM QTC4 NM1 ISSUE DATE 4 2 2018 NOTES...