QUANTECH
158
SECTION 9 - MAINTENANCE
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE 28 -
PRESSURE TRANSDUCER OUTPUT VOLTAGE (MEASURED SIGNAL TO RETURN AT THE
TRANSDUCER)
SUCTION PRESSURE TRANSDUCER
(125 PSIG)
DISCHARGE CONDENSER LIQUID PRESSURE AND
DISCHARGE PRESSURE TRANSDUCER
(400 PSIG)
PRESSURE
VOLTAGE
PRESSURE
VOLTAGE
0
0.50
0
0.50
5
0.66
25
0.75
10
0.82
50
1.00
15
0.98
75
1.25
20
1.14
100
1.50
25
1.30
125
1.75
30
1.46
150
2.00
35
1.62
175
2.25
40
1.78
200
2.50
45
1.94
225
2.75
50
2.10
250
3.00
55
2.26
275
3.25
60
2.42
300
3.50
65
2.58
325
3.75
70
2.74
350
4.00
75
2.90
375
4.25
80
3.06
400
4.50
85
3.22
90
3.38
95
3.54
100
3.70
105
3.86
110
4.02
115
4.18
120
4.34
125
4.50
Summary of Contents for QTC4 STYLE A Series
Page 22: ...QUANTECH 22 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...QUANTECH 34 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...QUANTECH 56 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 90: ...QUANTECH 90 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 148: ...QUANTECH 148 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 160: ...QUANTECH 160 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 163: ...QUANTECH 163 FORM QTC4 NM1 ISSUE DATE 4 2 2018 NOTES...