SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE 11 -
VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
PROTOCOL
BACNET MS/TP
MODBUS RTU5
N2
YORKTALK26
DE MODIFIER ADDRESS
0 to 41943(3)
1
N/A
-1
DE MODIFIER OFFSET
0 to 99(4)
0
N/A
N/A
P1 PROTOCOL
BACNET
N/A
N2
N/A
P1 MANUAL MAC ADDRESS
0-127(1)
N/A
0-127(1)
N/A
P1 BAUD RATE
9600 To 76800 or Auto
Selectable(1)
N/A
9600 or 19200
N/A
P1 PARITY
NONE
N/A
NONE
N/A
P1 STOP BITS
1
N/A
1
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127(1)
N/A
N/A
P2 BAUD RATE
N/A
19,200(2)
N/A
N/A
P2 PARITY
N/A
NONE(2)
N/A
N/A
P2 STOP BITS
N/A
1
N/A
N/A
P2 HW SELECT BIT
N/A
RS-485 or RS-232(1)
N/A
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
N/A
CHILLER ID
N/A
N/A
N/A
0
NOTES:
1.As Required By Network.
2.Or Other, as Required By Network.
3.Number Is Multiplied By 100, Set As Required By Network.
4. Number Is Added To DE Modifier Address, Set As Required By Network.
5. Unit Operating Software Version C.Mmc.13.03 Or Later Required For Modbus Protocol.
6. E-Link or SC-EQ interface requires YorkTalk2 setup.
TABLE 12 -
REAL TIME ERROR NUMBERS FOR
BAS, SC-EQ OR E-LINK COMMUNICATIONS CARD
ERROR
NUMBER (##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
RTC/BRAM INVALID
15
BACNET SETUP FAILED
The
above shows the real time
error numbers that may be encountered during commu-
nication setup, along with a description of each.
This data can be read and in some cases modified
using a BACnet, Modbus, or N2 network connection.
The BACnet Name is a 12 character or shorter name
used to identify the data in BACnet. The AI, AV, BI,
and BV columns are indexes used to select the data.
The AI, AV, BI, and BV number associated with a
BACnet Name should not be changed. If a value is
not wanted in this table, change the BACnet Name to
SPARE_XX_##. SPARE rows can be used for new
values.When set to BACnet or N2, communications
automatically sets Stop Bit (1) and Parity (None) for
port.
When connected via BAS and port is set for BACnet,
Modbus, or N2, the remote settings will continue to
follow the remote setpoints until the port is changed
to another protocol or DEmodifier address is set to -1.
The table below shows set-up requirements for each
communication protocol.
Summary of Contents for QTC4 STYLE A Series
Page 22: ...QUANTECH 22 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...QUANTECH 34 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...QUANTECH 56 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 90: ...QUANTECH 90 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 148: ...QUANTECH 148 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 160: ...QUANTECH 160 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 163: ...QUANTECH 163 FORM QTC4 NM1 ISSUE DATE 4 2 2018 NOTES...