88
www.qualitrolcorp.com
Matrix Controlled
provides a variety of input signal
configurations and logic to control the relay actuation. For example, using the math function
“or”, you can actuate the relay with a maximum of four different input signals. Conversely, by
using the “or” function and setting the Actuation Direction to “down”, you can actuate on the
minimum signal of the four control signals inputs.
The fields in this section of the
Output Relay Setup
window are described below.
Control
signal
“X”
(4 fields)
Allows you to select up to four input modules, relay states, and/or fiber
optic probes, the measured values of which, when compared to the
setpoints, actuate or de-actuate the relay according to the logic of the
matrix.
Setpoint
(4 fields)
Allows you to select a value corresponding to the control signal, which,
when it equals or exceeds the setpoint value, meets the conditions to
actuate the relay in that column.
Hysteresis
(4 fields)
Allows you to select a switching differential required to de-actuate the
relay. Without hysteresis, a relay could toggle on and off rapidly when the
control signal reaches the setpoint value, causing stress on relay circuits.
The hysteresis prevents this by providing a
“dead” band between on and
off.
Example:
If there is only one signal controlling the relay and the
Actuation direction
field (see below) is set to
“up”, when the control
signal reaches the setpoint value, the relay actuates. The relay de-
actuates only when the control signal falls below the setpoint value minus
the hysteresis.
Actuation
direction
(4 fields)
•
Select “up” to actuate the relay when the input signal becomes greater
than the setpoint value.
•
Select “down” to actuate the relay when the input signal becomes less
than the setpoint value.
Example:
You could use the
“up” actuation direction for rising temperature
values and the “down” actuation for alarming on low oil level values.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......