Calibrating the 509ITM
Calibrating Remote Outputs for Alternate Values
Overview and Requirements
Unless otherwise specified, the 509ITM remote output current loops are calibrated for 0 - 1
mA and 4 - 20 mA. If necessary, you can recalibrate the current loop outputs for the
following alternate values:
•
0 - 5 mA
•
0 - 10 mA
•
0 - 20 mA
This procedure provides steps for recalibrating the current loop outputs.
You will need the following items to perform this procedure:
•
509ITM
•
ammeter (or multi-meter set to measure DC milliamps)
•
Qualitrol Remote Software
Calibration Procedure
1.
Connect the computer to the 509ITM
The
Desktop Menu
window displays.
2. Click [Connect] and enter the password for the Calibrator tool.
Note:
If you do not know this password, call Qualitrol at 585-586-1515, Ext. 410.
3. Click [Start].