Tap Count
includes the fields described below.
Tap count
period
Allows you to select the number of hours within which you want to count
the total number of taps. This is a good indication of how much activity
the tap changer detects within a limited period of time. This is selectable
from 1 - 24 hours.
Previous
count/period
Displays the number of tap counts that occurred during the previous tap
count period.
Present
count/period
Displays the number of tap counts that have occurred during the present
tap count period. Upon completion of this tap count period, the present
count becomes the previous count, and a new present count begins.
Tap Motor Sensing
includes the fields described below.
Motor current
input module
Allows you to select an installed position of the input module, which
measures the motor current of the tap position changer.
Switch
contact
module 1
Allows you to select the installed position of the switch closure input
module, which detects when the tap changer motor actuates. This is only
if the 509 ITM installation uses a switch or relay contact for the actuation
detection.
Important:
If only one switch closure input module is used to detect
motor actuations, you must select it in this field and not in
the
Switch contact module 2
field.
Switch
contact
module 2
Allows you to select the installed position of a second switch closure
input module, which detects when the tap changer motor actuates. This
only occurs if the 509ITM installation uses two switch closure input
modules for the actuation detection (as in an up relay and a down relay).
This is an input module from 1 - 8, matching its location in the 509ITM.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......