111
www.qualitrolcorp.com
For more information about the learning mode and the initialization process, see
When you have completed the initialization process and have all of the parameter
information necessary, you can finish completing the
Cooling Bank Setup
window.
More Information
•
•
•
•
•
•
•
•
Setup
includes the fields described below.
Bank monitor
Indicates which cooling bank is to be configured. This field is for
informational purposes only.
Bank-
actuating
relay
Allows you to enter the actuating relay that starts the cooling system.
Example:
If the following conditions exist, this variable should be set to
“1”:
•
Input Module 1 measures the top oil.
•
The top oil temperature value controls when the cooling system
begins to operate.
•
Relay 1 is assigned to actuate when Input Module 1 exceeds the
setpoint.
Important:
This variable must be set correctly before using the
Cooling Monitor Initialization feature
. Do not use this relay