April 1, 2009

7014-101F

Page  7

d.  Temperature Calibration

The TEMPERATURE CAL screen is used to calibrate the 

temperature on the wall control.  If for some reason you feel 

the wall control is not accurately reading the temperature 

you  can  calibrate  it  to  a  thermostat  that  you  know  is  ac

-

curate.  Press the UP/DOWN buttons to the desired tem

-

perature.

c.  Temp Differential

The  TEMPERATURE  DIFFERENTIAL  screen  is  used  to 

change  the  set  default  temperature  differential.   This  sets 

how far below the set point the wall control allows the room 

temperature to fall before the appliance turns back on. It is 

usually set at time of installation.

Figure 7.1

e.  Properties

The PROPERTIES screen shows the version of software for 

the control board and wall control.  If you are placing a service 

call with your dealer, they may ask you to go to this screen 

and read them the information under “WC” and “SC”.

TEMPERATURE CAL

71.6 

O

F Cal Adj:

-13

DONE

SET

WC
SC
CB
CV

40h
6Bh
000
000

UFTI:  029
Rev:    004
TC:      -28

PROPERTIES

DONE

Figure 7.2

Figure 7.3

f.  Elevation

The ELEVATION screen allows you to adjust the appliance 

to  your  specific  elevation.  Press  the  UP/DOWN  buttons 

to  select  your  elevation.   The  message  in  the  center  will 

change between NORMAL and HIGH.  If you select HIGH, 

it will replace the normal fuel tables with specific high fuel 

tables.  You 

MUST

 select a fuel type after selecting HIGH.

Please  note  that  changing  the  elevation  will  delete  any 

custom or new fuel table loaded into the appliance.  You 

must  confirm  your  choice  on  the  CONFIRM  ELEVATION 

CHANGE screen.  This allows you to reverse your decision 

if necessary. 

 Figure 7.5.

ELEVATION

Over 4000 FT

Normal / High

Up to 4000 FT

DONE

Figure 7.4

g. Convection Blower Speed

The  CONV  BLOWER  SPEED  screen  allows  you  to  ad

-

just the blower speed to your individual preference. Press 

the UP/DOWN buttons to select your blower speed.  The 

message in the center will change between NORMAL and 

QUIET.
NORMAL allows the convection blower to reach maximum 

RPM at 135 degrees and QUIET at 165 degrees.

CONV BLOWER SPEED

Normal

Normal / Quiet

Quiet

DONE

Figure 7.6

CONFIRM ELEVATION CHANGE

YES

Changing elevations will

delete any custom or

new fuel tables loaded into

the stove.

Are you sure?

NO

Figure 7.5

Summary of Contents for SRV7000-451

Page 1: ...LE OF CONTENTS Check building codes prior to installation Installation MUST comply with local regional state and national codes and regulations Consult local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits CAUTION Hearth Home Technologies 1445 North Highway Colville WA 99114 Division of HNI INDUSTRIES CONTACT INFORMATION Please cont...

Page 2: ... is in start up cycle and is in the process of lighting an initial charge of fuel b SS LOW or SS MED SS soft start Indicates the soft start portion of the lighting sequence In these stages the fire begins to gradually build to operating temperature c AUTO x or MAN x x heat output level Indicates both the operating cycle automatic or manual and the current heat output level The heat output level wi...

Page 3: ...re of the room where the wall control is located The tempera ture displayed can be in units of Fahrenheit or Celsius The desired units can be selected via the system menu See Figure 6 5 on page 6 1 Set Comfort Level Temperature The most basic operation of the wall control is to turn the appliance on or off depending on the requirement for heat From the main screen the SET COMFORT LEVEL screen can ...

Page 4: ...esired fuel type and then press the button under Se lect The arrow will change to indicate the currently select ed fuel NOTE If you are burning a high ash fuel set the fuel selec tion to Utility Pellets When purchasing corn or wheat to burn in your appliance read the ingredient label very carefully Do NOT purchase fuel that contains any additives such as oils i e soybean oil and meals as it will r...

Page 5: ...aking changes or if you just en tered the programming screen to view the set program press Done or let the display return to the main screen automatically PROGRAM Full Week Wake 6 30 AM 68 F o Day 7 59 AM 68 F o Evening 4 00 PM 68 F o Night 11 00 PM 68 F o DONE SET NEXT PROGRAM Full Week Wake 6 30 AM 68 F o Day 7 59 AM 68 F o Evening 4 00 PM 68 F o Night 11 00 PM 68 F o DONE SET NEXT PROGRAM Full ...

Page 6: ...28 September 2007 28 Figure 6 1 Figure 6 2 Figure 6 3 6 User Settings Items that are rarely changed are stored under the USER SETTINGS a Temp Units F C The TEMP UNITS screen is used to change from Fahren heit to Celsius and back for the temperatures displayed b Flame Height Adjust The FLAME HEIGHT ADJUST screen is used to adjust the flame height fuel feed rate for specific installation and fuel ty...

Page 7: ... Figure 7 3 f Elevation The ELEVATION screen allows you to adjust the appliance to your specific elevation Press the UP DOWN buttons to select your elevation The message in the center will change between NORMAL and HIGH If you select HIGH it will replace the normal fuel tables with specific high fuel tables You MUST select a fuel type after selecting HIGH Please note that changing the elevation wi...

Page 8: ...e Turning on appliance 7 Fill the hopper with fuel If the hop per was completely empty or has run out of fuel put approximately 1 2 cup of pellets into the firepot for a quick restart 8 Be sure the hopper lid and glass door are both closed 1 At the starting screen press MENU Function Buttons Buttons Up Down READY 73 Set at 73 12 30 PM HEAT OUTPUT MENU Room Temp Wall Control for Reference 6 Press D...

Page 9: ...Temp SERVICE RETRY ERROR LIST 1 If the appliance has stopped operat ing check the wall control screen If it is showing Min Firepot Temp the hopper has run out of fuel 2 Fill the hopper with fuel and press the RETRY button twice The first time turns on the back light the sec ond time starts the retry function 3 If the wall control screen changes to a SHUTDOWN screen that means your appliance has no...

Page 10: ...ly approved fire starting gel to start the fire The high burn rate is no longer available on battery back up Each level drops down one level i e the high burn be comes medium high burn and so on If the battery charge falls below 10 volt it can no longer sustain the appliance operation and the appliance will shut down You must disconnect and reconnect the bat tery to start it up again Recommended B...

Page 11: ...Pull the feed system and inspect Clear jam and then press Retry button MISSED IGNITION Igniter bad or poor harness connection Out of fuel or fuel is bridging in hopper Faulty firepot thermocouple connection is shorted Check connections if OK replace igniter Break up bridging pellets Refill hopper Replace the thermocouple press Retry MIN FIREPOT TEMP Out of fuel Refill hopper Add handful of pellets...

Page 12: ...774802 6796302 6840261 6848441 6863064 6866205 6869278 6875012 6880275 6908039 6919884 D320652 D445174 D462436 Canada 1297749 2195264 2225408 2313972 Australia 780250 780403 1418504 or other U S and foreign patents pending Date purchased installed Serial Number Location on appliance Dealership purchased from Dealer phone Notes We recommend that you record the following pertinent information for yo...

Reviews: