Quadra-Fire QV36A-FB Owner'S Manual Download Page 5

5

Quadra-Fire  •  Expression 36 (QV36A-FB)  •  2062-900  Rev. S  •  11/11

G. Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in 
whole or in part for residential purposes, including those 
owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) 
feet above fi nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following 
requirements shall be satisfi ed:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fi tter 
shall observe that a hard wired carbon monoxide detector 
with an alarm and battery back-up is installed on the fl oor 
level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas fi tter shall observe that 
a battery operated or hard wired carbon monoxide detec-
tor with an alarm is installed on each additional level of 
the dwelling, building or structure served by the side wall 
horizontal vented gas fueled equipment. It shall be the 
responsibility of the property owner to secure the services 
of qualifi ed licensed professionals for the installation of 
hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic, 
the hard wired carbon monoxide detector with alarm and 
battery back-up may be installed on the next adjacent 
fl oor level.
In the event that the requirements of this subdivision can 
not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply 
with the above requirements; provided, however, that dur-
ing said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA 
720 and be ANSI/UL 2034 listed and IAS certifi ed. 

Signage

A metal or plastic identifi cation plate shall be permanent-
ly mounted to the exterior of the building at a minimum 
height of eight (8) feet above grade directly in line with the 
exhaust vent terminal for the horizontally vented gas fu-
eled heating appliance or equipment. The sign shall read, 
in print size no less than one-half (1/2) inch in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-
STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon-
tally vented gas fueled equipment shall not approve the 
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 
through 4. 

Exemptions

The following equipment is exempt from 248 CMR 
5.08(2)(a)1 through 4: 

•  The equipment listed in Chapter 10 entitled “Equip-

ment Not Required To Be Vented” in the most current 
edition of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure sep-
arate from the dwelling, building or structure used in 
whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 
horizontally vented gas equipment provides a venting 
system design or venting system components with the 
equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system 
shall include:

•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the fl ue gases, but identifi es 
“special venting systems”, the following requirements 
shall be satisfi ed by the manufacturer:

•  The referenced “special venting system” instructions 

shall be included with the appliance or equipment in-
stallation instructions; and 

•  The “special venting systems” shall be Product Ap-

proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation 
instructions. 

A copy of all installation instructions for all Product Ap-
proved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting 
instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion 
of the installation. 

See Gas Connection section for additional Common-
wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 
document.

Summary of Contents for QV36A-FB

Page 1: ...OT DISCARD Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation In the Commonwealth of Massachusetts installation...

Page 2: ...Information Listing Label Information Location Gas and Electric Information Serial Number Type of Gas The model information regarding your specific appliance can be found on the rating plate usually...

Page 3: ...nstalling Non combustible Facing Material 22 8 Installing Vent Pipe A Assembly of Vent Sections 23 B Disassembly of Vent Sections 25 C Installing Heat Shield and Horizontal Termination Cap 26 D Instal...

Page 4: ...dered non combustible materials E Combustible Materials Specification Materials made of or surfaced with wood compressed paper plant fibers plastics or other material that can ig nite and burn whether...

Page 5: ...ed heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas ins...

Page 6: ...kaging The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipmen...

Page 7: ...ght fracture lines or spider webbing on the surface of the material Cracks that are less than 1 32 in wide and less than 3 in long If cosmetically unacceptable such cracks may be repaired with the SRV...

Page 8: ...access Locate appliance away from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see figure 3 1...

Page 9: ...inside a chase Construction of the chase may vary with the type of build ing These instructions are not substitutes for the require ments of local building codes Local building codes MUST be checked C...

Page 10: ...Ceiling Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of Appliance Inches 10 52 17 1 4 41 1 2 32 1 2 0 0 1 1 2 36 Millimeters 254 1321 438 1054 825 0 0 25 13 914 WAL...

Page 11: ...ltiple Vertical Termination Figure 4 2 specifies minimum vent heights for various pitched roofs See Figure 4 4 for specific clearances 3 foot minimum in snow regions HORIZONTAL OVERHANG VERTICAL WALL...

Page 12: ...ches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3...

Page 13: ...re 5 1 Figure 5 1 5 5 Vent Information and Diagrams A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams C Measuring Standards Vertical and horizontal measure...

Page 14: ...Maximum V1 H1 30 ft 9 1 m Maximum Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between ceiling firestops ALWAYS maintain specified clearances around venting and firestop syste...

Page 15: ...1 ft 6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft 6 in 18 ft 7 ft 6 in 21 ft HT 21 ft Max VT 40 ft Max VT HT 30 ft Max Note A section of vertical pipe 12 inc...

Page 16: ...e horizontal component is less than 5 feet then the total vent run can be extended to 40 feet VT Min HT Max 1 ft 6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft...

Page 17: ...Min HT Max 1 ft 6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft 6 in 18 ft 7 ft 6 in 21 ft HT 21 ft Max VT 40 ft Max VT HT 30 ft Max Note A section of vertical...

Page 18: ...o heat shield is necessary If your local inspector requires the wall shield firestop on both sides then both wall shield firestops must have a heat shield attached to them Fire Risk Explosion Risk Mai...

Page 19: ...tic Shield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling see Figure 6 4 Secure with th...

Page 20: ...one Cover Plate to the top of the appliance Figure 7 1 Remove Screws 2 Bend the four pre cut tabs up to expose the top of the appliance Place the Heat Zone cover plate on the insulation inside the uni...

Page 21: ...intain specified clearances around the appliance Do NOT notch into the framing around the appliance spacers Failure to keep insulation framing or other material away from the appliance may cause fire...

Page 22: ...Figure 7 9 Attaching Non combustible Facing Material D Installing Non combustible Facing Material Center and attach two top boards to the framing members See Figure 7 10 Use fasteners from fastener pa...

Page 23: ...nd the seams are not aligned see Figure 8 5 Tug slightly on sectionAto confirm it has completely locked into place It is acceptable to use screws no longer than 1 inch to hold outer pipe sections toge...

Page 24: ...slip section is too long the inner and outer flues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be c...

Page 25: ...aced 120 apart may be used to do this see Figure 8 9 Horizontal Sections Horizontal sections of vent must be supported every 5 feet with a vent support or plumber s strap Figure 8 9 Securing Vertical...

Page 26: ...ion codes Figure 8 13 Venting through the Wall Burn Risk Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap Fire Hazard Impaired performance o...

Page 27: ...burner operation HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARGE OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISC...

Page 28: ...m collar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to complete storm collar assem bly see Figure 8 18 Slide the assembled storm col...

Page 29: ...fire condition Low pressure may cause explosion Verify minimum pressures when other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig...

Page 30: ...eck with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve compartment and connected to t...

Page 31: ...econstruction The battery pack requires two D cell batteries not includ ed Batteries cannot be placed in the battery pack while using the 3 volt AC transformer Conversely the trans former must be unpl...

Page 32: ...10 120 VAC source for added features the fireplace may have installed Electrical ratings for the control box are 110 VAC 60 Hz and is required for operation of this device Installation precautions Thi...

Page 33: ...h Once a location is chosen and the electrical box is installed proceed as follows Install the provided control wire from the fireplace to the switch location Use caution not to stress the wire around...

Page 34: ...lace at 20 F over set point and turn it back on at 20 F below set point Up and Down Arrows Push to adjust set point temperature under automatic control AUX Auxiliary Button Button Press Turns on auxil...

Page 35: ...tions and reattach the cover plate to the outer shell If the box is being wired from the INSIDE of the appliance Remove the screw attaching the junction box receptacle to the outer shell rotate the ju...

Page 36: ...must not interfere with Air flow through grilles or louvers Operation of louvers or doors Access for service 14 IN 23 IN 12 IN MIN 18 IN MIN 12 IN MAX 1 IN MAX 3 IN MIN Risk of Fire Non combustible c...

Page 37: ...ement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interferes with proper burner operation Placing the Ember Material...

Page 38: ...UTION Logs are fragile Figure 12 1 1 1 6 6 5 5 4 4 3 3 2 2 Carefully remove the grate from the foam sup ports and then remove the foam supports from around the burner Figure 12 2 Place grate on the ba...

Page 39: ...hat the bottom of the log conforms with the contour of the burner The outside of the log should rest on the grate The front of the log will rest against the right andiron LOG 1 SRV2062 701 Place log 1...

Page 40: ...the bottom of log 6 should rest on the wedge shape on the end of log 3 LOG 5 SRV330 704 Place the Y end of log 5 against the corre sponding bump on log 3 The other end of the log should rest in the s...

Page 41: ...he bottom of the glass door toward the firebox with slight upward pressure Latch the bottom spring latches securely onto the bottom glass door tabs G Burner Removal Only for Servicing Loosen the shutt...

Page 42: ...g the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the appliance to soot If sooting occurs the air shutter will need to be opened by...

Page 43: ...replacement should be done by qualified technician Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provid...

Page 44: ...TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL...

Page 45: ...nce will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapors and liquids c...

Page 46: ...ged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC b A s...

Page 47: ...uity with a multimeter with ohms set at lowest range e Faulty module Turn ON OFF rocker switch or wall switch to OFF posi tion Remove ignitor wire I from module Place ON OFF Rocker switch or wall swit...

Page 48: ...Handle glass assembly with care Note Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door A...

Page 49: ...f firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterior...

Page 50: ...nsions Use for reference only For framing dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions Location Inches Millimeters L 37 1 4 945 M 8 3 8 212 N 30 1 2 776 O 36 1 8 916 P...

Page 51: ...76 to 610 10 1 2 in 267 mm 10 7 8 in 276 mm 45 7 3 8 in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm 12 in...

Page 52: ...at shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is great...

Page 53: ...5 8 in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 35...

Page 54: ...iginal purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HH...

Page 55: ...OW RI QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG...

Page 56: ...___________________________ ________________________________________________________________________________ ________________________________________________________________________________ __________...

Reviews: