background image

26

u

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 26.  Vent Termination Minimum Clearances

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances to window or door

that may be opened, or to per-
manently closed window.

D*

= 24" ....................... vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-
cated above the terminal

    *60” min. ............... for vinyl clad soffits and below

electrical service

F

=  9" ......................... clearance to outside corner

G

= 6" .......................... clearance to inside corner

H

= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ....... clearance to gas service regu-

lator vent outlet

J

= 9" (U.S.A.)

12" (Canada) ......... clearance to non-mechanical air

supply inlet to building or the
combustion air inlet to any other
appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

air supply inlet

L** = 7 ft. ......................... clearance above paved

sidewalk or a paved driveway
located on 

public

 property

M*** = 24" ......................... clearance under veranda,

porch, deck or balcony

N

= 6” ........................... non-vinyl sidewalls

12” ......................... vinyl sidewalls

O

= 24” ......................... non-vinyl soffit and overhang

60” ......................... vinyl soffit and overhang

P

= 8 ft.

CAUTION: 

IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE

INSTALLED.

  ** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor.

NOTE 1

: On private property where termination is less than 7 feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2. 

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination
cap. 

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

O

N

P

R

Q

(See Note 1)

(See Note 1)

(See Note 2)

S =  6" MIN. .................. clearance from sides of elec-

trical service

T = 12" MIN. ................. clearance above electrical

service

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

    

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

(See Note 5)

(See Note 5)

Electrical

Service

V

S

V

S

V

T

D*

V

NOTE 3

: Local codes or regulations may require different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity to

doors or other traffic areas.

NOTE 5: 

Location of the vent termination must not interfere with

access to the electrical service.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permitted

in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.

Quadra-Fire assumes no responsibility for the improper perfor-
mance of the fireplace when the venting system does not meet
these requirements.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

Summary of Contents for QV-ST

Page 1: ...FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...onents 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 The Gas Control Systems 28 Step 6 The Gas Supply Line 28 Step 7 Gas Pressure Requirements 28 Step 8 Wir...

Page 4: ...LP Exploded Parts Diagram Vue clat e des pi ces Part number list on following page La liste des num ros de pi ce se trouve la page suivante Service Parts 1 2 3 4 10 6 7 9 8 6 7 9 8 12 11 5 Log Set As...

Page 5: ...S Orifice de br leur GN 32DMS 573 800 Burner Orifice LP 1 8mm Orifice de br leur PL 1 8mm 501 801 Junction Box Bo tier de d rivation 100 250A Piezo Ignitor Allumage Pi zo 291 513 Thermopile Thermopile...

Page 6: ...LP Exploded Parts Diagram Vue clat e des pi ces Part number list on following page La liste des num ros de pi ce se trouve la page suivante Service Parts 6 7 9 8 6 7 9 8 1 2 3 4 10 11 11 5 Log Set As...

Page 7: ...3 800 Burner Orifice LP 1 8mm Orifice de br leur PL 1 8mm 501 801 Junction Box Bo tier de d rivation 100 250A Piezo Ignitor Allumage Pi zo 291 513 Thermopile Thermopile 060 512 Thermocouple Thermocoup...

Page 8: ...odes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedro...

Page 9: ...instructions will void the own er s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Hearth Home Technologies disclaims any responsibility for the following actio...

Page 10: ...LLE SIDE GLASS DOOR END GLASS DOOR TOP STANDOFFS TOP GRILLE TOP VENT COLLARS FRONT RIGHT SIDE LEFT SIDE 13 331mm 24 1 4 616mm 12 1 8 308mm VENT COLLARS 42 3 4 1086mm 28 7 8 735mm ELECTRICAL ACCESS 2 1...

Page 11: ...RICAL ACCESS GAS LINE ACCESS GAS CONTROLS LABELS BOTTOM GRILLE TOP GRILLE TOP STANDOFFS GLASS DOOR 45 1143mm 13 330mm 12 1 8 308mm VENT COLLARS 24 1 4 616mm 28 7 8 733mm 2 1 2 64mm GAS LINE ACCESS 4 1...

Page 12: ...t before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace facing material The dia gram below shows framing reference dimensions CAUTION...

Page 13: ...4 41 1 2 23 1 4 45 29 7 8 QV PIER 43 1 4 44 41 1 2 23 1 4 45 29 7 8 Figure 4 Framing Dimensions NOTE DIMENSIONSSHOWNININCHES Shows center of 12 x 12 vent framing holes for top and rear venting The ce...

Page 14: ...inch inner pipe 8 5 8 inch outer pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Page 15: ...nd the venting configuration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to...

Page 16: ...16 Figure 7 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M STRAIGHT OUT HORIZONTAL VENTING H Max Run 24 610 mm Figure 8 Straight Out Horizontal Venting H V CAP...

Page 17: ...2 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 86m 17 MAX 5 1m H 17 MAX 5 1m V H 37 MAX 11 3m Figure 10 Venting with One 90 Elbow V H 1 MIN 305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m...

Page 18: ...MIN 1 22m 12 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 86m 17 MAX 5 1m 17 MAX 5 1m V H 37 MAX 11 3m Figure 11 Venting with Two 90 Elbows VENTING WITH TWO 2 90 ELBOWS V FT H FT 1 MIN 305mm 3 MAX 914m 2 M...

Page 19: ...X 2 7 m 4 MIN 1 22 m 8 MAX 2 48 m 12 MAX 3 6 m 8 MAX 2 48 m 17 MAX 5 1 m V H H1 37 MAX 11 3m Figure 12 Venting with Two 90 Elbows Figure 13 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V F...

Page 20: ...m 4 MIN 1 22 m 8 MAX 2 48 m 15 MAX 4 5 m 8 MAX 2 48 m 17 MAX 5 1 m V H H1 H2 37 MAX 11 3m VENTING WITH THREE 3 90 ELBOWS V H H H1 H2 1 MIN 305 mm 2 MAX 610 mm 3 MAX 914mm 2 MIN 610 mm 4 MAX 1 22 m 6 M...

Page 21: ...MIN 1 22m 12 MAX 3 6m 17 MAX 5 1m NOTE H H1 17 MAX 5 1m V V1 H H1 37 MAX 11 3m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 1 MIN 305mm 3 MAX 914m 2 MIN 610mm 6 MAX 1 86m 3 MIN 914mm 9 MAX 2 7m 4 MIN...

Page 22: ...16 Follow the vent configuration tables accordingly Remove the insulation from the REAR five inch flue pull the heat shield out from outside of the firebox WARNING THE TOP HEAT SHIELD INSIDE THE FIREB...

Page 23: ...e firestops Figure 20 12 x 12 Hole and Vent Pipe Figure 21 Heat Shield Interior Exterior Firestops VENT PIPE 1 25 4 mm 12 305mm 12 305mm TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIO...

Page 24: ...iling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 23 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an att...

Page 25: ...ermination cap to its final exterior position on the building WARNING THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP For trapezoidal cap termination kits Using screws secure t...

Page 26: ...ne side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes...

Page 27: ...of the building Roof Pitch H min ft flat to 6 12 1 0 6 12 to 7 12 1 25 over 7 12 to 8 12 1 5 over 8 12 to 9 12 2 0 over 9 12 to 10 12 2 5 over 10 12 to 11 12 3 25 over 11 12 to 12 12 4 0 over 12 12 t...

Page 28: ...he shut off valve When attaching the pipe support the control so that the lines are not bent or torn Step 7 Gas Pressure Requirements Pressure requirements for Hearth Home Technolo gies gas fireplaces...

Page 29: ...anently installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF s...

Page 30: ...D A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE P...

Page 31: ...lace dime size pieces of ember material about 1 2 inch apart near port holes in burner top Do NOT press em bers into burner ports Cover the top of the burner with a single layer of ember material For...

Page 32: ...the control in the PILOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every sec...

Page 33: ...in the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operat...

Page 34: ...ntrol compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check o...

Page 35: ...he pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Page 36: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Page 37: ...accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation...

Reviews: