Quadra-Fire PS35-C Installation Manual Download Page 15

15

09/20

7058-804C

Vent Information

A. Venting Termination Minimum 

Requirements

J or K

X

V

M

I

H

A

V

G

B

V

V

A

B

V

F V

C

B

B

E

L

V

D

V

Electrical

Service

V

N

V

N

V

N

N

V

Inside Corner

FIXED 

CLOSED

OPEN

OPEN

FIXED 

CLOSED

V

X

G

G

Termination Cap

Air Supply Inlet

Gas Meter

Restricted Area

O

P

A

12 in.

Above Finish Grade (the grade surface 

must be a non-combustible material

B

12 in.

48 in. no OAK

Open door or window: below or to the side

B

12 in.

Open door or window: above

C

6 in.

Permanently closed window: above, below 

or to the side

D

18 in.

36 in. no OAK

Vertical clearance to a ventilated soffi  t 

located above the terminal within a hori-

zontal distance of 2 ft from the center-line 

of the terminal 

E

12 in.

Clearance to unventilated soffi  t

F

12 in.

Clearance to outside corner

G

12 in.

Clearance to inside corner

H

36 in.

Above gas meter/regulator measured from 

horizontal center-line of regulator

I

36 in. USA

72 in. Canada

Clearance to service regulator vent outlet

J

12 in.

48 in. no OAK

Clearance to non-mechanical air supply 

inlet to the building or the combustions air 

inlet to any other appliance

K

10 ft horizontal

3 ft vertical

Clearance to mechanical air supply

L

7 ft.

Above paved sidewalk, paved driveway 

located on 

public

 property

M

12 in.

Under an open veranda, porch, deck or 

balcony

N

See Note 

below*

Electric service: above, below or to the 

side (location must not obstruct or interfere 

with access)

O

24 in.

Adjacent building, fences and protruding 

parts of the structure

P

12 in.

Clearance above roof line for vertical 

terminations

All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.

24 in.

Above grass, top of plants, wood or any other combus-

tible

12 in.

36 in. no OAK

Clearance from any forced air intake of other appliance

12 in.

Clearance horizontally from combustible wall

15 in.

Vented directly through a wall, minimum length of 

horizontal pipe

6 in. horizontal

12 in. vertical

Minimum horizontal or vertical terminations must pro-

trude from wall

*NOTE: 

Consult local building, fi re offi  cials or authorities 

having jurisdiction. Local codes or regulations 

may require diff erent clearances.

NOTICE:

 Termination must exhaust above air 

inlet elevation.

•  It is recommended that at least 60 inches (1.52m) of 

vertical pipe be installed when appliance is vented 

directly through a wall. This will create a natural draft, 

which will help prevent the possibility of smoke or 

odor venting into the home during a power outage. 

•  It will also keep exhaust from causing a nuisance 

or hazard by exposing people or shrubs to 

high temperatures.

•  The safest and preferred venting method is to extend 

the vent vertically through the roof or above the roof.

NOTICE: Do NOT Terminate Vent:

• 

In any location that will allow fl ue gases or soot from 

entering or staining the building.

•  In any location which could create a nuisance 

or hazard.

•  In any enclosed or semi-enclosed area such as a 

carport, garage, attic, crawl space, under a sun deck 

or porch, narrow walkway.

•  Closely fenced area, or any location that can build up 

a concentration of fumes such as a stairwell, covered 

breezeway, etc.

Summary of Contents for PS35-C

Page 1: ...esult causing property damage personal injury or death WARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If app...

Page 2: ...Started A Design Installation Location Considerations 5 B Thermostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and...

Page 3: ...ted Efficiency 68 8 EPA BTU Output 8 600 to 29 700 per hour BTU Input 12 600 to 41 900 per hour Vent Size 3 or 4 Type L or PL Hopper Capacity 45 lbs Fuel Premium Wood Pellets Weighted average LHV Low...

Page 4: ...composed of any combination of the following Steel Plaster Brick Iron Concrete Tile Glass Slate Materials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube...

Page 5: ...ir safe operation Do NOT install damaged incomplete or substitute components NOTICE Check building codes prior to installation Installation MUST comply with local regional state and national codes and...

Page 6: ...the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Risk of Fire Damaged parts could impair safe operation Do N...

Page 7: ...ng this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check...

Page 8: ...ns Figure 8 3 Front View Figure 8 1 Top View Figure 8 2 Side View 2 1 4 in 59mm 2 1 4 in 59mm 8 7 8 in 224mm 8 7 8 in 224mm 9 1 2 in 243mm 12 1 2 in 318mm 20 1 4 in 514mm 31 3 4 in 806mm 22 1 4 in 565...

Page 9: ...o 4 inch Offset Adapter 811 0720 Figure 9 4 Side View w Top Vent Adapter TPVNT 5 3 to 4 inch Offset Adapter 811 0720 Figure 9 1 Top View w Top Vent Adapter TPVNT 5 3 in 77mm 5 in 128mm 11 1 8 in 284mm...

Page 10: ...2 Side View w Top Vent Adapter TPVNT 5 3 to 6 inch Offset Adapter 812 3570 Figure 10 4 Side View w Top Vent Adapter TPVNT 6 11 1 8 in 284mm 4 1 4 in 109mm 7 3 8 in 189mm 3 in 77mm 2 7 8 in 74mm 2 7 8...

Page 11: ...Vent Adapter TPVNT 6 3 to 4 inch Offset Adapter 811 0720 Figure 11 2 Side View w Top Vent Adapter TPVNT 6 3 to 4 inch Offset Adapter 811 0720 8 7 8 in 224mm 3 1 4 in 81mm 3 1 4 in 81mm 5 1 4 in 132mm...

Page 12: ...Back Wall to Adapter 1 25 E Side Wall to Appliance 14 356 F Back Wall to Appliance 6 1 4 159 Corner Installation Inches Millimeters G Walls to Appliance 2 51 Vertical Installation Inches Millimeters...

Page 13: ...r protection extending beneath the flue pipe is required with horizontal venting or under the Top Vent Adapter with vertical installation Figure 13 1 Figure 13 2 Figure 13 3 Figure 13 4 C Hearth Pad R...

Page 14: ...Depth n a n a 48 1219 D To Side Wall 14 356 n a n a All minimums listed are to a combustible surface A C B B D Table 14 1 Figure 14 2 Figure 14 1 NOTE Illustrations reflect typical installations and...

Page 15: ...parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in A...

Page 16: ...d may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to dete...

Page 17: ...cessful draft include Preventing negative pressure Location of appliance and chimney E Minimum Vacuum Requirements 065 inches W C F Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 7...

Page 18: ...re 18 2 1 Locate the calculated equivalent feet of pipe on the vertical left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If you fall...

Page 19: ...D VENT The following may occur The appliance will not vent properly Smoke spillage in the house Excessive sooting CAUTION Straight Out 45 Degree NOTICE Please note that while the minimum clearance for...

Page 20: ...tructions for all reduced air clearances installations B Vertical into Existing Class A Chimney Figure 20 3 Figure 20 2 D Through The Wall Vertical External C Vertical Interior Typical Installation PR...

Page 21: ...T WARNING Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Fireclay Flue Liner with Airs...

Page 22: ...re 22 2 1 Measure distance from floor to air vent opening in appliance and mark location on wall 2 Use a saw to cut opening in wall 2 inch kit Cut a 2 1 2 to 3 inch opening on inside wall and a 3 to 3...

Page 23: ...et using the 2 holes already in the short horizontal pipe in the top vent adapter as a guide Install the 2 screws Figure 23 1 6 Install the vent pipe into the top vent adapter 7 To clean the top vent...

Page 24: ...the thermostat from the mounting plate by gently pulling the two pieces apart c Slide thermostat wires through the back of the mounting plate Figure 24 3 d Connect your thermostat wire to the terminal...

Page 25: ...UTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED Do NOT cut through Floor joist wall studs or ceiling trusses Any supporting material that would affect...

Page 26: ...26 09 20 7058 804C A Service Maintenance Log 8 Reference Materials Date of Service Performed By Description of Service...

Page 27: ...27 09 20 7058 804C Date of Service Performed By Description of Service...

Page 28: ...28 09 20 7058 804C Date of Service Performed By Description of Service...

Page 29: ...29 09 20 7058 804C Date of Service Performed By Description of Service...

Page 30: ...Vertical Runs Only PEL DAMP3 Y Damper 4 PEL DAMP4 Outside Air Kit 3 OAK 3 Outside Air Kit 2 811 0872 Hose Alum Flex 2 Inch X 3 Ft 3 Ft SRV200 0860 Outside Air Cap Assembly 7001 044 Outside Air Collar...

Page 31: ...it 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Bolt Hex Head Pkg of 10 25221A 10 Y Guide Pin Sleeve Pkg of 25 31120 25 Y Hurricane Screw Pkg of 40 SRV2005 861 40 Nut SER FL SMALL 1 4 20 Pkg of 24 226 0...

Page 32: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Reviews: