background image

January 

4, 

2018 

     7082-150C 

       

 

 

 

 

17

MT VERNON E2 INSERT-C

NOTE:  

Check clearances carefully for this type of instal-

lation to ensure adequate room for outside air venting.

Check building codes prior to installation.

•  Installation MUST comply with local, regional, state and 

national codes and regulations.

•  Consult local building, fire officials or authorities having juris

-

diction about restrictions, installation inspection, and permits.

CAUTION

NOTE:

  In Canada only a full reline is allowed per ULC 

S628, ORD ULC C1482-M1990.

B.  Full Reline With Outside Air - Vertical 

Figure 17.1

NOTE:  Use metal plate around 

exhaust vent pipe and seal all edges 

with non-flammable insulation such 

as fiberglass, mineral wool or 

ceramic.

Do not use high temperature 

caulking materials to seal any edge 

to prevent future serviceability.

Outside Air

Termination at

Chimney Top

(Vertical)

12 in [305mm]

min. below

12 in [305mm]

min. below

NOTE:  

In Canada this fireplace insert must be installed 

with a continuous chimney liner extending from the fire

-

place insert to the top of the chimney.  The chimney liner 

must conform to the Class 3 requirements of CAN/ULC-

S635, Standard for Lining Systems for Existing Masonry 

or Factory-Built Chimneys and Vents, or CAN/ULC-S640, 

Standard for Lining Systems for New Masonry Chimneys.

Summary of Contents for MTVI-E2-MBK-C

Page 1: ...ot store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing...

Page 2: ...Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearance To Combustibles US Canada 8 C Minimum Opening for Masonry Zero Clearance Fireplaces 9 D Hearth Extension 9 E Floo...

Page 3: ...9 Amps Run 2 45 Amps E Mobile Home Approved This appliance is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided The stru...

Page 4: ...of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney of...

Page 5: ...on unless installing into an existing masonry fireplace B Tools And Supplies Needed C Inspect Appliance and Components Open the appliance and remove all the parts and articles packed inside the Compon...

Page 6: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Page 7: ...605mm 26 7 8 in 683mm 11 7 8 in 302mm 24 1 8 in 613mm 33 in 838mm 50 in 1270mm 34 1 2 in 876mm 45 in 1143mm 11 3 4 in 297mm 18 1 2 in 469mm Figure 7 2 Front View with Cast Panel Set 23 7 8 in 606mm 32...

Page 8: ...or choice must be added to this dimension B Clearance To Combustibles US Canada Figure 8 1 Built in Appliance Rear Vent NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONL...

Page 9: ...4 inches Minimum Opening Dimensions Inches Millimeters A Height 24 3 8 619 B Front Width Steel Panel Set 32 1 4 819 Front Width Cast Panel Set 32 1 4 819 C Back Width 24 1 8 613 D Depth Steel Panel Se...

Page 10: ...250 2061 WARNING THIS FIREPLACE MAY HAVE BEEN ALTERED TO ACCOMMODATE AN INSERT IT MUST BE RETURNED TO ITS ORIGINAL CONDITION BEFORE USE AS A SOLID FUEL BURNING FIREPLACE 250 2061 Heath Home Technolog...

Page 11: ...lace was tested prior to 1998 a full height listed chimney liner must be installed from the appliance flue collar to the chimney top The liner must be securely attached to the insert flue collar and t...

Page 12: ...lk paved driveway located on public property M 12 in Under an open veranda porch deck or balcony N See Note below Electric service above below or to the side location must not obstruct or interfere wi...

Page 13: ...demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional ventilation...

Page 14: ...nstruction of the structure Mechanical exhausting devices E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It can be vented vertically...

Page 15: ...to the equivalent feet of pipe calculated previously and the altitude above sea level of this installation Figure 15 2 a Locate the calculated equivalent feet of pipe on the vertical left side of the...

Page 16: ...side combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams...

Page 17: ...Air Vertical Figure 17 1 NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insulation such as fiberglass mineral wool or ceramic Do not use high temperature caulking...

Page 18: ...space such as an attic or garage Figure 18 1 Collar Wire Ties Trim Ring Termination Cap 3 inch Aluminum Flex Pipe not included Figure 18 2 OAK Exploded View Lower the leveling bolts if necessary to k...

Page 19: ...cast trim header 2 cast trim footers left and right 1 fastener package Tools Needed Powered Phillips head screw driver 1 Remove contents from box being careful not to scratch or damage the cast trim p...

Page 20: ...crews provided Figure 20 3 Back of Top Surround Back of Side Surround Screws Figure 20 1 Shown with trim installed on panel set G Optional Log Set Placement Instructions 2 PIECE LOG SET INSTALLATION 1...

Page 21: ...e located on an inside wall approximately 5 up from the floor W R Saturday and Sunday can be programmed individually by changing the format from 5 2 to 5 1 1 To change the format 1 Press and hold the...

Page 22: ...ermostat should be located on an inside wall approximately 5 up from the floor PROGRAMMABLE THERMOSTAT PART WALL STAT P W R Saturday and Sunday can be programmed individually by changing the format fr...

Page 23: ...es when burning on high A prop erly adjusted fire will burn cleaner and have higher efficiencies Please copy and paste the follow web address http www quadrafire com Owner Re sources Use and Care Vide...

Page 24: ...4 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 24 1 CAUTION Never draw outsi...

Page 25: ...January 4 2018 7082 150C 25 MT VERNON E2 INSERT C A Service and Maintenance Log Date of Service Performed By Description of Service 8 Reference Materials...

Page 26: ...26 7082 150C January 4 2018 MT VERNON E2 INSERT C Date of Service Performed By Description of Service...

Page 27: ...nly LOGS 60 AE B Y Outside Air Kit OAK 3 Top Vent Adapter TPVNT 4 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim SP MTVS GD Component Pack 7036 042...