MT VERNON AE INSERT

F.  Equivalent Feet of Pipe 

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent size.  

Figure 15.1.

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Example of 3 Elbow-Rear Vent Termination Calculation

Pellet Venting 

Component

# of 

Elbows

Feet of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components

Equivalent Feet

90

o

 Elbow or Tee

3

X

5

15

45

o

 Elbow

X

3

Horizontal Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

Note:  This is a generic example and is not 

intended to represent any specific fuel type.

Vent surfaces get HOT, can cause burns if 

touched.  Non-combustible shielding or guards 

may be required.

WARNING

Figure 15.2

3 in. or 4 in. (76mm or 102mm) Diameter  Pipe 

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET 

20 

30 

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only 

10 

Example 1

Example 2

Example 1

:  If the equivalent length of pipe is 23 feet (7m) with 

altitude of 8,000 feet (2438m) you must use 4 inch (102mm) 

diameter type “L” or “PL” vent.

Example 2

:  If the equivalent length of pipe is 12 feet (3.7m) 

with altitude of 6,000 feet (1829m) you may use 3 or 4 inch 

(76 to 102mm) diameter type “L” or “PL” vent.

G.  Pipe Selection Chart 

The chart will help you in determining proper venting size 

according to the equivalent feet of pipe calculated previously 

and the altitude above sea level of this installation.  

Figure 15.2

a.  Locate the calculated equivalent feet of pipe on the vertical 

left side of the chart.  

b.  Move to the right horizontally on the chart until you reach 

your altitude above sea level.

c.  If you fall below the diagonal line, 3 or 4 inch (76 to 102mm) 

pipe may be used.  

d.  If it is anywhere above the diagonal line, a 4 inch (102mm) 

diameter pipe is required.

NOTICE:

 

•  A 90° elbow is 5 times as restrictive to the flow of exhaust 

gases under positive pressure as 1 foot (305mm) of hori

-

zontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a foot of 

vertical pipe.

Figure 15.1

WARNING

 RISK OF INJURY OR PROPERTY DAMAGE!

•  Improper installation, adjustment, alteration, service or main

-

tenance can cause injury or property damage. 

•  Refer to the owner’s information manual provided with this 

appliance. 

•  For assistance or additional information consult a qualified 

installer, service agency or your dealer.

Fire Risk.
•  Only LISTED venting components may be used.
•  NO OTHER vent components may be used.

•  Substitute or damaged vent components may impair safe 

operation.

WARNING

Summary of Contents for MTVERNINSAE-MBK

Page 1: ...oline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warr...

Page 2: ...4 E Chimney and Exhaust Connection 14 F Equivalent Feet of Pipe 15 G Pipe Selection Chart 15 5 Venting Systems 16 A Full Reline With Outside Air Horizontal 16 B Full Reline With Outside Air Vertical 1...

Page 3: ...appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Operati...

Page 4: ...t be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize the use of chimney offsets Place the appliance where there will be a clear passage for a Li...

Page 5: ...rol is an integral part of the appliance No other wall control or thermostat can be substituted D Inspect Appliance and Components Open the appliance and remove all the parts and articles packed insid...

Page 6: ...o the party responsible for use and operation ATTENTION INSTALLER Follow this Standard Work Checklist This standard work checklist is to be used by the installer in conjunction with not instead of the...

Page 7: ...nd Set 36 5 8 932 15 380 13 1 8 333 12 7 8 327 32 814 23 7 8 606 3 5 8 92 3 5 8 92 23 7 8 606 32 813 13 330 15 1 8 384 13 330 36 3 4 932 45 1143 34 1 2 876 50 1270 33 838 29 3 4 756 23 7 8 605 11 3 4...

Page 8: ...earances to Combustibles UL and ULC Fire Risk Comply with all minimum clearances to combusti bles as specified WARNING Failure to comply may cause house fire Figure 8 1 Built in Appliance Framing Dime...

Page 9: ...010mm Figure 9 2 HEARTH EXTENSION No thermal protection required Ember protection only If mantel depth is 10 inches or less than the height from the hearth to the bottom of the mantel is 39 3 4 inches...

Page 10: ...BURNING FIREPLACE 250 2061 Heath Home Technologies 250 2061 5 5 in width x 2 in height NON ANOD ALUM BLACK LETTERS ON SILVER with 1 8 in holes on both sides Black letters Figure 10 1 If the hearth ext...

Page 11: ...himney cap must be re installed after installing the approved chimney liner meeting type UL 103 HT requirements 2100 F per UL 1777 If the chimney is not listed as meeting HT requirements or if the fac...

Page 12: ...es and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in t...

Page 13: ...space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house Vent Configurations When installing a pellet appliance wit...

Page 14: ...imney NOTICE HEARTH Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Down drafts Tight sealing...

Page 15: ...829m you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculate...

Page 16: ...raw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations d...

Page 17: ...ide Air Vertical Figure 17 1 Outside Air Termination at Chimney Top Vertical 305mm min below 305mm min above NOTE Use metal plate around exhaust vent pipe and seal all edges with non flammable insula...

Page 18: ...g on outside of house 3 Use wire ties to secure flex pipe to collar assembly 4 Slide trim ring over flex pipe and run pipe through wall 5 Attach flex pipe not included to outside termination cap with...

Page 19: ...then release the latch The latch hooks onto a bracket to hold the side in place Bend tabs down Shipped flat from the factory Figure 19 2 9 attachment holes 3 on each side and 3 in the front Figure 19...

Page 20: ...tabs down Included in Surround Kit 2 side panels left and right 1 panel top 1 fastener package Included in Cast Trim Kit 2 cast trim legs left and right 1 cast trim header 2 cast trim footers left an...

Page 21: ...Control Thermostat Installation 1 When mounting the wall control thermostat on the wall be sure to follow your wall control s installation instruc tions carefully NOTE The wall control thermostat sho...

Page 22: ...0 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 22 1 CAUTION Never draw outside combust...

Page 23: ...3 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim No Longer Available SP MTVS GD Component Pack 7036 042 Trim Panel Set Gold SRV250 4660 Surround St...

Page 24: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: