17
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06
Figure 7.
Vent System Components and Termination Kits
Step 3. Installing the Vent System
A. Vent System Approvals
These models are approved to use DVP series direct vent
pipe components and terminations (see Figures 6 and 7).
Approved vent system components are labeled for identifi-
cation. This pipe is tested and listed as an approved com-
ponent of the fireplace. The pipe is tested to be run inside
an enclosed wall. There is no requirement for inspection
openings at each joint within the wall. There is no required
pitch for horizontal vent runs.
NO OTHER VENTING SYS-
TEMS OR COMPONENTS MAY BE USED
.
Detailed installation instructions are included with each vent
termination kit and should be used in conjunction with this
Installers Guide
.
The flame and ember appearance may vary based on the
type of fuel burned and the venting configuration used.
Identifying Vent Components
The vent systems installed on this gas fireplace may in-
clude one, two, or three 90°
elbow assemblies. The rela-
tionships of vertical rise to horizontal run in vent configura-
tions using 90° elbows
MUST BE
strictly adhered to. The
rise to run relationships are shown in the venting drawings
and tables. Refer to the diagrams on the next several pages.
NOTE: Two 45° elbows may be used in place of one
90° elbow. Rise to run ratios in the vent system must
be followed if 45° elbows are used.
This model has 45
0
elbow built into this unit. It may be
positioned to vent either horizontal or vertical. Depending
on the installation, decide which direction the elbow should
be facing. Remove the 8 screws from the corner cover plate.
Position the 45
0
elbow as desired and replace the corner
cover plate with the 8 screws.
PVK-80
DVP-TRAP
DVK-01D
DVK-TVCD
DVP-TVHW
Termination kits
DVP-TB1
HORIZONTAL
TERMINATION
WALL FIRESTOP
90 DEGREE
ELBOW
PIPE LENGTH
CEILING
FIRESTOP
VERTICAL
TERMINATION
STORM COLLAR
ROOF FLASHING
(IPI models only)