background image

Quadra-Fire  •  QVI-25FB  •  2031-900  Rev. F  •  9/07

21

Troubleshooting

With proper installation, operation, and maintenance your gas appliance will
provide years of trouble-free service.  If you do experience a problem, this
troubleshooting guide will assist a qualified service person in the diagnosis
of a problem and the corrective action to be taken. This troubleshooting
guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1.

 After repeated

triggering of the red

or black piezo button,

the spark ignitor will

not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode wire is

properly connected, replace the ignitor.

b. Defective pilot or
misaligned electrode

(spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or
black piezo button again. If the pilot lights, an improper gas/air mixture caused the
bad lighting and a longer purge period is recommended. If the pilot will not light,

ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a
strong spark. If the gap is OK, replace the pilot.

c. No gas or low gas

pressure.

Check the remote shut-off valvess from the fireplace. Usually, there is a valve near

the gas main. There can be more than one (1) valve between the fireplace and the

main.

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.

  The pilot will not

stay lit after carefully

following the lighting

instructions.

a. Defective

thermocouple.

Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the

pilot for maximum flame impingement.

Ensure that the thermocouple connection at the gas valve is fully inserted and tight

(hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt meter lead wire on

the tip of the thermcouple and the other meter lead wire on the thermocouple

copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less

than 15mV, replace the thermocouple.

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

3.

 The pilot is

burning, there is no

gas burner, the valve

knob is in the ON
position, and the

ON/OFF switch is in

the ON position.

a. ON/OFF switch or
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the jumper
wires across the terminals at the switch. If the burner comes on, replace the
defective switch. If the switch is OK, place the jumper wires across the switch wires
at the gas valve. If the burner comes on, the wires are faulty or connections are

bad.

b. Thermopile may
not be generating

sufficient millivoltage.

If the pilot flame is not close enough physically to the thermopile, adjust the pilot

flame.

Be sure the wire connections from the thermopile at the gas valve terminals are

tight and that the thermopile is fully inserted into the pilot bracket.

Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP

terminals of the gas valve. The meter should read 325 millivolts minimum, while

holding the valve knob depressed in the pilot position, with the pilot lit, and the

ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is

below the specified minimum.

With the pilot in the ON position, disconnect the thermopile leads from the valve.
Take a reading at the thermopile leads. The reading should be 325 millivolts

minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON

position. Check the millivolt meter a the thermopile terminals. The millivolt meter

should read greater than 125mV. If the reading is acceptable, and if the burner
does not come on, replace the gas valve.

d. Plugged burner
orifice.

Check the burner orifice for stoppage. Remove stoppage.

e. Wall switch or
wires are defective.

Follow the corrective action in Symptom and Possible Cause 1.a above. Check

the switch and wiring. Replace where defective.

5

Summary of Contents for FireBrick qvi25fb

Page 1: ...AGE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFOR MATION CONSULT A QUALIFIED IN STALLER SERVICE AGENCY OR THE GAS SUPPLIER READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS...

Page 2: ...ce front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warran...

Page 3: ...t System 9 Step 2 Positioning Leveling and Securing the Insert 13 Step 3 The Gas Control Systems 13 Step 4 The Gas Supply Line 13 Step 5 Gas Pressure Requirements 14 Step 6 Wiring the Appliance 14 Wir...

Page 4: ...Quadra Fire QVI 25FB 2031 900 Rev F 9 07 4 4 2 1 3 5 6 Part number list on following page Log Set Assembly Service Parts Diagram Service Parts QVI 25FB 16 7 8 10 9 12 13 15 14 11...

Page 5: ...Glass Door Assembly GLA 2019 Y 15 Glass Latch Assembly QTY 2 Req 339 121A 16 Access Plate 2019 116 Surround Mount Right 2019 205 Surround Mount Left 2019 196 Junction Box 040 250A Y Blower Assembly O...

Page 6: ...320A Y Valve NG 060 522 Y Valve LP 060 523 Y Wiring Assembly 2020 059 Y Gasket Pilot Bottom 2019 161 Gasket Pilot Top 768 432 Orifice NG 36B 567 801 Y Orifice LP 52B 074 801 Y IMPORTANT THIS IS DATED...

Page 7: ...ed in accordance with local codes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models...

Page 8: ...EN SION IF PRESENT MUST COMPLY WITH EI THER OF THE FOLLOWING 1 THE SOLID FUEL BURNING APPLIANCE MANUFACTURER S SPECIFICATION OR 2 LOCAL BUILDING CODES REQUIRED BY AUTHORITY HAVING JURISDICTION WARNING...

Page 9: ...AIR STARTING COLLAR EXHAUST STARTING COLLAR ON OFF SWITCH 4 3 8 20 3 8 1 1 16 2 13 16 2 9 11 16 3 5 8 REF 3 7 16 2 5 16 1 9 16 14 7 16 29 1 8 22 570 14 3 4 18 15 16 15 GAS INLET 5 9 16 1 1 16 14 5 8 Q...

Page 10: ...d the maximum vertical rise is 50 feet These dimensions are measured from the starting collars of the unit to the end of the last section of vent pipe See dimension V in Figure 3 Vent System Approvals...

Page 11: ...E THE ROOF TOP THESE MINIMUM HEIGHTS ARENECESSARYINTHEINTEREST OF SAFETY SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST 2 FEET FROM A VER TICAL WALL AND 2 FEET...

Page 12: ...THE INLET AIR COLLAR OF THE UNIT AND EITHER ATTACHED TO THE INLETAIRCOLLAROFTHETERMINATIONCAP OR TERMINATED IN THE CHIMNEY This option shows both exhaust and inlet air vent pipes attached to the adapt...

Page 13: ...KING HANDLE SLIDING PLATE STAINLESS STEEL ADAPTER FOR EXHAUST MUST BE INSTALLED INLET AIR VENT PIPE 3 INCH COLLAR OPTIONAL LINK ZC ADPB For Flashing Class A Pipe TERMINATION CAP SQUARE FLASHING REMOVE...

Page 14: ...building codes to properly size the gas supply line leading to the 1 2 inch 13 mm hook up at the unit This gas appliance is designed to accept a 1 2 inch 13 mm gas supply line To install the gas suppl...

Page 15: ...NECT REMOTE CONTROLS IF AB SENT FOR EXTENDED TIME PERIODS THIS WILL PRE VENT ACCIDENTAL APPLIANCE OPERATION For Standing Pilot Ignition Wiring Appliance Requirements This appliance DOES NOT require 11...

Page 16: ...ACKET Figure 10 RUBBER GROMMETS FAN ATTACH GROUND WIRE COVER PLATE Fan Option This product accepts an optional blower GFK 160A Instal lation of this blower requires 110 VAC power supplied to the elect...

Page 17: ...les in burner top see Figure 12 Space dime size ember pieces about a 1 2 inch apart Never press embers into burner ports DO NOT cover burner ports Place dime size pieces around front and sides of burn...

Page 18: ...w minutes for the lines to purge themselves of this air Once the purging is complete the appliance will light and will operate normally Subsequent lightings of the appliance will not require this purg...

Page 19: ...LOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every second The piezo makes a...

Page 20: ...vacuum the control compartment appliance logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Page 21: ...copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts re...

Page 22: ...necessary e Improper vent cap installation Check for proper installation and freedom from debris or blockage 6 Glass soots a Flame impingement Adjust the log set so that the flame does not excessivel...

Page 23: ...years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable item...

Reviews: