Quadra-Fire CASTILE-B Installation Manual Download Page 15

15

08/22

7021-801F

C. Negative Pressure

NOTE

: The appliance exhaust outlet is designed to 

accommodate 3 inch venting. Use of 4 inch venting 

requires the use of a 3-to-4 inch exhaust vent increaser 

in addition to any other venting components needed, sold 

separately.

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods

•  Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

• 

Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 

-

Recessed lighting

 

-

Attic hatch

 

-

Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion appliances 

and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design
•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and seams 

taped or sealed

D. Draft

Draft is the pressure difference needed to vent an appliance 

successfully. When an appliance is drafting successfully, all 

combustion byproducts are exiting the home through the 

chimney.
Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:
•  Preventing negative pressure
•  Location of appliance and chimney

E. Chimney and Exhaust Connection 

1. 

Chimney & Connector:

  Use  3  or  4  inch  (76-102mm) 

diameter type “L” or “PL” venting system. It can be 

vented vertically or horizontally.

NOTE: 

Follow venting manufacturers recommendations 

for sealing pipe joints.

NOTICE:

  Hearth  &  Home  Technologies  assumes  no 

responsibility for the improper performance of the chimney 

system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 

fumes and soot.

WARNING

2. 

Mobile Home:

 Approved for all Listed pellet vent. If 

using  the  3  inch  (76mm)  vertical Top  Vent Adapter  Kit 

or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, 

use  Listed  double  wall  flue  connector.  A  Quadra-Fire 

Outside Air Kit must be used with manufactured home 

installations.

3. 

Residential:

  The  3  inch  (76mm)  vertical  Top  Vent 

Adapter Kit and the 3 to 6 inch (76 to 152mm) Top Vent 

Offset Adapter are tested to use 24 gauge single wall flue 

connector or Listed double wall flue connector to Class 

A Listed metal chimneys, or masonry chimneys meeting 

International Residential Code standards for solid fuel 

appliances.

4.  Install  vent  at  clearances  specified  by  the  vent 

manufacturer.

5. 

Seal exhaust venting system to the unit with High Temp 

500ºF RTV silicone sealant. Secure the venting system 

to the unit with at least (3) screws. All pellet vent pipe 

must be secured together either by means provided by 

the pipe manufacturer or by (3) screws at each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST 

VENTING SYSTEM OF THIS Appliance.

7. DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

USE ONLY RECOMMENDED VENTING COMPONENTS; 

OTHERWISE MAKESHIFT PARTS MAY RESULT IN 

PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH. 

WARNING

Summary of Contents for CASTILE-B

Page 1: ...ction about restrictions installation inspection and permits CAUTION WARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not ov...

Page 2: ...ls And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearances to Combustibles UL and ULC 10 C Hearth Pad Require...

Page 3: ...tions to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certification 175 19 EPA Certified Emissions 1 1 grams...

Page 4: ...erial that can ignite and burn flame proofed or not plastered or non plastered H Sleeping Room When installed in a sleeping room it is recommended that 3ft of vertical be installed prior to horizontal...

Page 5: ...fficient additional support to meet this weight requirement prior to installation The weight of the appliance is 208 lbs Installation MUST comply with local regional state and national codes and regul...

Page 6: ...all the parts and articles packed inside the Component Pack Inspect all the parts and glass for shipping damage Report to your dealer any parts damaged in shipment All labels have been removed from th...

Page 7: ...ng this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check...

Page 8: ...op View with TPVNT 6 and 811 0720 5 3 4 in 146mm 3 1 2 in 89mm Figure 8 2 Top View with TPVNT 2 and 812 3570 5 in 127mm 11 7 8 in 297mm 3 in 76mm 1 3 4 in 44mm Figure 8 4 Top view with TPVNT 2 and 811...

Page 9: ...Figure 9 4 Side View with TPVNT 2 and 811 0720 28 5 8 in 727mm 27 in 686mm Figure 9 3 Side View with TPVNT 6 and 811 0720 24 1 2 in 622mm 22 7 8 in 581mm Figure 9 2 Side View 22 7 8 in 581mm 17 in 43...

Page 10: ...preference Horizontal Through the Wall Inches Millimeters A Back Wall to Appliance 2 51 B Side Wall to Appliance 6 152 Corner Installation Inches Millimeters C Walls to Appliance 2 51 C C A B Vertical...

Page 11: ...m to both sides of the fuel loading door Open the door and measure 6 inches 152mm from the side edge of the opening in the face of the appliance See exception CAUTION Hearth and Home Technologies does...

Page 12: ...a All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation...

Page 13: ...e P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of pla...

Page 14: ...mands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to t...

Page 15: ...sful draft include Preventing negative pressure Location of appliance and chimney E Chimney and Exhaust Connection 1 Chimney Connector Use 3 or 4 inch 76 102mm diameter type L or PL venting system It...

Page 16: ...ch your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe is required Pel...

Page 17: ...ust use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall or partition of comb...

Page 18: ...4 in 610mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit B Vertical into Existing Class A Chimney We recommend a min...

Page 19: ...1 in 25mm clearance with firestop 6 in 152mm minimum Fireclay Flue Liner with airspace Concrete Cap Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of...

Page 20: ...aw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or garage CAUTION 4 Measure distance from floor to air vent opening in appliance and mark location on wall U...

Page 21: ...t Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Install the vent pipe into the adapter Follow ve...

Page 22: ...ends are held ALL the way into the terminal block while the screws are being tightened 7 Snap the thermostat to the base plate 6 There are two AA ALKALINE ONLY batteries already installed into the the...

Page 23: ...rasive nature of a pellet appliance fire the logs are not covered under warranty Any placement variation other than shown here can cause excessive heat and shall void the appliance warranty E Leg Leve...

Page 24: ...Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 7 7 Mobile Home Installation Products of combustion generate carbon monoxide and different fuels generate differ...

Page 25: ...25 08 22 7021 801F A Service and Maintenance Log Date of Service Performed By Description of Service 8 8 Reference Materials...

Page 26: ...26 08 22 7021 801F Date of Service Performed By Description of Service...

Page 27: ...llar Offset Top Vent 812 3570 Damper 3 Inch Tall Vertical Installs Only PEL DAMP3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Outside Air Kit Rear 811 0872 Channel Air Intake SRV413 7040 Cov...

Page 28: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Reviews: