19
09/20
7074-803C
A. Through The Wall
Horizontal termination cap must be a minimum of 6
inches. (152mm) from the wall. Approved for mobile home
installations. Must use 3 or 4 inch (76-102mm) “L” or “PL”
listed pellet venting or Listed double wall pipe and an
authorized Outside Air Kit in mobile homes.
Figure 19.1
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
Wall
Thimble
Horizontal
Termination
Cap
2 in.
(51mm)
Minimum
6 in.
(152mm)
Minimum
from glass
Wall
Thimble
Illustration shows venting going in both directions.
Choose which one is best for your installation.
2 in. (51mm)
Minimum
2 in.
(51mm)
Minimum
6 in (152mm) Minimum
6 in
(152mm)
Minimum
Figure 19.2
5
Venting Systems
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired,
the installation shall conform to
CAN/CSA-B365
We strongly recommend that you DO NOT
DOWNWARD VENT.
The following may occur:
• The appliance will not vent properly
• Smoke spillage in the house
• Excessive sooting
CAUTION
Straight Out
45 Degree
NOTICE:
Please note that while the minimum clearance
for the termination cap is 6 inches (152mm)
there is the possibility of soot build-up around
the termination area. If this occurs we suggest
to move the termination further away from the
house to prevent it.