16
August,
2018 7037-181A
11
4300 Millennium NZ Wood Appliance
B. Minimum Height of Flue System Exit
Figure 11.1
increase as necessary until nothing
within 3000mm of fluetop
increase from
1000mm minimum
until clear within
3000mm of flue top
any nearby structure
3000mm
3000mm
3000mm
or less
more than 3000mm
600mm
minimum
NOTICE:
• Chimney performance may vary.
•
Trees, buildings, roof lines and wind conditions affect
performance.
• Chimney height may need adjustment if smoking or
overdraft occurs.
NOTICE:
Locating the appliance in a basement or in a location
of considerable air movement can cause intermittent
smoke spillage from appliance. Do not locate
appliance near
• Frequently open doors
• Central heat outlets or returns