Page  10

7033-308B

January 17, 2013

R

3100 Series ACC Wood Burner

C L

 

D

ra

w

in

no

t t

sca

le

 

12

 

Tested flue systems, as per AS/NZS 2918:2001

 

 

 

 

 

 

 

Fig. 5

ADD Cowl

 

 

 

Casing Cover

 

 

Spider Bracket

 

oversized casing cover 

is necessary

 

 

minimum 25mm gap 

between flue pipe casing & 

combustible material

 

 

Non combustible material 

Hebel block or 12mm 

Promina board or similar 

under the flashing

 

 

 

 

25 

25

 

 

Approved Flashing

 

 

Roof Line

 

 

Inner Casing 200mm 

above roof line

 

 

 

Outer Casing

 

 

Inner Casing

 

 

25 

Internal Swage

 

 

 

 

 

25 

25

 

 

 

 

 

12.5

 

 

Vented

 

Ceiling Plate

 

 

 

 

 

 

Pioneer 

Double Flue 

Shield

 

 

Flue Pipe

 

 

 

 

 

 

 

 

 

 

 

CL  

C L

 

 

 

 

 

 

Quadra-fire Millennium

 

 

 

 

 

 

 

Floor

 

Protector

 

The flue crimp must be cut so the swage 

(half-moon bulge after the crimp) fits 

tightly into the spigot.

FLUE PENETRATION

Fig. 7

Summary of Contents for 31ST-ACC-AU

Page 1: ...ue systems as per AS NZS 2918 2001 Appendix F with a ceiling angle between 0 30 inclusive For installations with a ceiling angle greater than 30 refer to Fig 7 8 and AS NZS 2918 2001 4 6 3 b Ceiling P...

Page 2: ...enjoyment in the warmth and comfort of your hearth appliance Thank you for choosing Quadra Fire 3100 Series ACC JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2012 2013 2014 INSTALLATION DATE QUADRA...

Page 3: ...308B Page 3 R 3100 Series ACC Wood Burner Quadra Fire 3100 Millenium ACC Wood Burner Dimensions 616 mm 533 mm 254 mm 457 mm 273 mm 397 mm 379 mm 484 mm 635 mm 581 mm 170 mm 749 mm 90 mm 25 mm 499 mm...

Page 4: ...e tested and comply with the minimum Floor Protector requirements of AS NZS 2918 2001 Note The minimum Floor Protector sizes are specified in the clearance chart see Table 1 2 A Floor Protector can in...

Page 5: ...ction from corner wall 756 E Min floor protector front width 800 F Min overall floor protector depth 1469 CORNER POSITIONING 45 Table 2 Fig 4 FIREBOX INSTALLATION 1 If a separate floor protector is be...

Page 6: ...8B January 17 2013 R 3100 Series ACC Wood Burner Quadra Fire 31 Step Top ACC Wood Burner Dimensions 678mm 618mm 391mm 292mm 406mm 527mm 870mm 635mm 318mm 237mm C L 457mm 606mm 841mm 194mm 537mm 264mm...

Page 7: ...e tested and comply with the minimum Floor Protector requirements of AS NZS 2918 2001 Note The minimum Floor Protector sizes are specified in the clearance chart see Table 3 4 A Floor Protector can in...

Page 8: ...ction from corner wall 661 E Min floor protector front width 800 F Min overall floor protector depth 1335 CORNER POSITIONING 45 Table 4 Fig 6 FIREBOX INSTALLATION 1 If a separate floor protector is be...

Page 9: ...cceptable Solution from 01 07 05 5 Install the outer casing so that i lower end is flush with the underside of the ceiling material and ii with the addition of metal L brackets affix to the outer casi...

Page 10: ...bustible material Non combustible material Hebel block or 12mm Promina board or similar under the flashing 25 25 Approved Flashing Roof Line Inner Casing 200mm above roof line Outer Casing Inner Casin...

Page 11: ...6 downward distance of casing and 3 x flue distance of the ceiling plate ADD Cowl Casing Cover Spider Bracket Approved Flashing A Ceiling Plate Batten A 3 x flue pipe Ceiling flue pipe Fig 7 ADD Cowl...

Page 12: ...the entral tongue to locate inside the flue outlet only Two tabs are provided and if folded back at 90 degrees the bracket and Flue Mounted Shield will mount lower onto the appliance The Flue Mounted...

Page 13: ...CTION IS CONSIDERED THE MAN UFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE CAUTIONS CRACKED AND BROKEN COMPONENTS e g GLASS PANELS OR CERAMIC TILES MAY RENDER THE INSTALLATION UNSAFE WARNING ANY...

Page 14: ...Page 14 7033 308B January 17 2013 R 3100 Series ACC Wood Burner Service And Maintenance Log Date of Service Performed By Description of Service...

Page 15: ...January 17 2013 7033 308B Page 15 R 3100 Series ACC Wood Burner Service And Maintenance Log Date of Service Performed By Description of Service...

Page 16: ...STOVE DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these inst...

Reviews: